Rack System/E power distribution components

AC power is distributed to the Rack System/E rack through Power Distribution Units (PDU) mounted on the

two vertical rails in the rear of the rack. Up to four PDUs can be mounted in the rack—two mounted

on the right side of the cabinet and two mounted on the left side.
Each of the PDU power cables has an AC power source specific connector. The circuit breaker-controlled

PDU outputs are routed to a group of ten AC receptacles. The storage system components plug directly

into the PDUs.

Rack AC power distribution

The power distribution configuration in a Rack System/E rack depends on the number of storage systems

installed in the rack. If one storage system is installed, only two PDUs are required. If multiple storage

systems are installed, four PDUs are required.
The site AC input voltage is routed to each PDU mounted in the rack. Each PDU distributes AC through

ten receptacles directly to the storage system components.

PDUs 1 and 3 (optional) are mounted on the left side of the cabinet. Grey power cords connect

these PDUs to the number 1 drive enclosure power supplies and to the controller enclosures.

PDUs 2 and 4 (optional) are mounted on the right side of the cabinet. Black power cords connect

these PDUs to the number 2 drive enclosure power supplies and to the controller enclosures.