2 plc setpoints and actual values – NORD Drivesystems BU0550 User Manual
Page 88
PLC logic for NORD SK 54xE frequency inverters
88
BU 0550 GB-0813
Index
Name
Function
Standardisation
Type
Access
6
_6_Delay_digital_inputs
State of digital inputs according
to P474
Bit 0: DIN1
Bit 1: DIN2
Bit 2: DIN3
Bit 3: DIN4
Bit 4: DIN5
Bit 5: DIN6
Bit 6: DIN7
Bit 7: Digital function AIN1
Bit 8: Digital function AIN2
INT
R
7
_7_Analog_input1
Value of analog input 1 (AIN1)
10.00V = 1000
INT
R
8
_8_Analog_input2
Value of analog input 2 (AIN2)
10.00V = 1000
INT
R
9
_9_Analog_input3
Value of analog function DIN2
10.00V = 1000
INT
R
10
_10_Analog_input4
Value of analog function DIN3
10.00V = 1000
INT
R
11
_11_External_analog_input1
Value of analog input 1 (1.IOE)
10.00V = 1000
INT
R
12
_12_External_analog_input2
Value of analog input 2 (1.IOE)
10.00V = 1000
INT
R
13
_13_External_analog_input3
Value of analog input 1 (2.IOE)
10.00V = 1000
INT
R
14
_14_External_analog_input4
Value of analog input 2 (2.IOE)
10.00V = 1000
INT
R
15
_15_State_analog_output
Status of analog output
10.0V = 100
BYTE
R
16
_16_State_ext_analog_out1
Status of analog output (1 IOE)
10.00V = 1000
INT
R
17
_17_State_ext_analog_out2
Status of analog output 2 (2 IOE)
10.00V = 1000
INT
R
Table 104 Input and output process values
4.2.2
PLC setpoints and actual values
The process values listed here form the interface between the PLC and the frequency inverter. The function
of the PLC setpoints is specified in (P553).
NOTE
The process value _20_PLC_control_word overwrites the function block MC_Power. The PLC
setpoints overwrite the function blocks MC_Move…. and MC_Home.
Index
Name
Function
Standardisation
Type
Access
20
_20_PLC_control_word
PLC control word
Corresponds to USS profi-
le
INT
R/W
21
_21_PLC_set_val1
PLC setpoint 1
100% = 4000h
INT
R/W
22
_22_PLC_set_val2
PLC setpoint 2
100% = 4000h
INT
R/W
23
_23_PLC_set_val3
PLC setpoint 3
100% = 4000h
INT
R/W
24
_24_PLC_set_val4
PLC setpoint 4
100% = 4000h
INT
R/W
25
_25_PLC_set_val5
PLC setpoint 5
100% = 4000h
INT
R/W
26
_26_PLC_additional_control_word1
PLC additional control
word 1
Corresponds to USS profile
INT
R/W
27
_27_PLC_additional_control_word2
PLC additional control
word 2
Corresponds to USS profile
INT
R/W
28
_28_PLC_status_word
PLC status word
Corresponds to USS profile
INT
R/W
29
_29_PLC_act_val1
PLC actual value 1
100% = 4000h
INT
R/W
30
_30_PLC_act_val2
PLC actual value 2
100% = 4000h
INT
R/W
31
_31_PLC_act_val3
PLC actual value 3
100% = 4000h
INT
R/W
32
_32_PLC_act_val4
PLC actual value 4
100% = 4000h
INT
R/W
33
_33_PLC_act_val5
PLC actual value 5
100% = 4000h
INT
R/W