3 control terminals – NORD Drivesystems BU0550 User Manual
Page 80
PLC logic for NORD SK 54xE frequency inverters
80
BU 0550 GB-0813
4.1.3
Control terminals
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P418
… [-01]
…
… [-03]
Analog output func.
(Analog output function)
S
P
0 ... 60
all { 0 }
Analog functions (max. load: 5mA analog):
An analog voltage (0 ... +10 Volt) can be taken from the control terminals (max. 5mA). The
following scaling applies for the PLC setting:
- PLC value : 0 = 0V
- PLC value : 100 = 10.0V
[-01] = Analog output (int. AOUT), no function as factory setting,
AOUT of frequency inverter, control terminal 17
[-02] = First IOE (ext. AOUT1), no function as factory setting,
AOUT of the 1st IO extension module (SK xU4-IOE)
[-03] = Second IOE (ext. AOUT2), no function as factory setting,
AOUT of the 2nd IO extension module (SK xU4-IOE)
Setting:
…
60 = Value from PLC: the value comes from the PLC