NORD Drivesystems BU0550 User Manual
Page 56
PLC logic for NORD SK 54xE frequency inverters
56
BU 0550 GB-0813
3.5.2.5
MC_MoveRelative
Except for the input DISTANCE this is identical to MC_MoveAbsolute. The setpoint position results from the
addition of the present actual position and the transferred DISTANCE.
Table 75 MC_MoveRelative
3.5.2.6
MC_MoveAdditive
Except for the input DISTANCE this is identical to MC_MoveAbsolute. The setpoint position results from the
addition of the present setpoint position and the transferred DISTANCE.
Table 76 MC_MoveAdditive
VAR_INPUT
VAR_OUTPUT
Input
Explanation
Type
Output
Explanation
Type
EXECUTE
Enable
BOOL
DONE
Specified setpoint position reached
BOOL
DISTANCE
Setpoint position
DINT
BUSY
Setpoint position not reached
BOOL
VELOCITY
Setpoint frequency
INT
COMMAND-
ABORTED
Command aborted
BOOL
MODE
Mode source is the setpoint
position
BOOL
ERROR
Error in FB
BOOL
ERRORID
Error code
INT
ERRORID
Explanation
0
No error
1000h
FI is not enabled
1200h
Position control not activated
1201h
The High position has not been entered in the PLC setpoints (P553)
1202h
The Low position has not been entered in the PLC setpoints (P553)
VAR_INPUT
VAR_OUTPUT
Input
Explanation
Type
Output
Explanation
Type
EXECUTE
Enable
BOOL
DONE
Specified setpoint position reached
BOOL
DISTANCE
Setpoint position
DINT
BUSY
Setpoint position not reached
BOOL
VELOCITY
Setpoint frequency
INT
COMMAND-
ABORTED
Command aborted
BOOL
MODE
Mode source is the setpoint
position
BOOL
ERROR
Error in FB
BOOL
ERRORID
Error code
INT
ERRORID
Explanation
0
No error
1000h
FI is not enabled
1200h
Position control not activated
1201h
The High position has not been entered in the PLC setpoints (P553)
1202h
The Low position has not been entered in the PLC setpoints (P553)