3 AWL (Instruction List, IL)
BU 0550 GB-0813
57
3.5.2.7
MC_Home
Causes the frequency inverter to start a reference point run if EXECUTE changes from 0 to 1 (flank). The
frequency inverter moves with the setpoint frequency entered in VELOCITY. The direction of rotation is
reversed if the input with the position reference signal (P420[-xx] = Reference point) becomes active. With
the negative flank of the position reference signal the value in POSITION is adopted. Then the frequency
inverter brakes to 0Hz. The DONE signal changes to 1. During the entire HOME run the BUSY output is
active.
If the MODE input is set to 1, the FI remains at the middle of the initiator after a home run.
If the process is interrupted (e.g. by another MC function module), COMMANDABORTED is set.
In case of error, ERROR is set to 1. In this case, DONE is 0. The corresponding error code in the ERRORID
applies.
Table 77 MC_Home
3.5.2.8
MC_Power
The output stage of the frequency inverter can be switched on or off via this function. The output stage is
enabled if the ENABLE input is set to 1. The prerequisite for this is that the FI is in the status "Switch-on
block" or "Standby". If the FI is in the status "Error" or "Error reaction active", the fault must first be remedied
and acknowledged. Only then can enabling be carried out via this block. Switch-on is also not possible if the
frequency inverter is in the status "Not on standby". In all cases the FB goes into error status and ENABLE
must be set to 0 in order to acknowledge the error.
The frequency inverter is switched off if the ENABLE input is set to 0. If this happens while the motor is
running, it is first run down to 0Hz via the ramp set in P103.
The STATUS is 1, if the output stage of the frequency inverter is switched on. Otherwise it is 0.
ERROR and ERRORID are reset, if ENABLE is switched to 0.
Table 78 MC_Power
VAR_INPUT
VAR_OUTPUT
Input
Explanation
Type
Output
Explanation
Type
EXECUTE
Enable
BOOL
DONE
Specified setpoint position reached
BOOL
POSITION
Setpoint position
DINT
BUSY
Home run active
BOOL
VELOCITY
Setpoint frequency
INT
COMMAND-
ABORTED
Command aborted
BOOL
MODE
Home mode
BOOL
ERROR
Error in FB
BOOL
ERRORID
Error code
INT
ERRORID
Explanation
0
No error
1000h
FI is not enabled
1200h
Position control not activated
1201h
The High position has not been entered in the PLC setpoints (P553)
1202h
The Low position has not been entered in the PLC setpoints (P553)
VAR_INPUT
VAR_OUTPUT
Input
Explanation
Type
Output
Explanation
Type
ENABLE
Enable
BOOL
STATUS
Motor is supplied with current
BOOL
ERROR
Error in FB
BOOL
ERRORID
Error code
INT
ERRORID
Explanation
0
No error
1001h
Stop function is active
1300h
The FI is not in status "Standby" or "Switch-on block"