beautypg.com

NORD Drivesystems BU0550 User Manual

Page 44

background image

PLC logic for NORD SK 54xE frequency inverters

44

BU 0550 GB-0813

3.5.1.1

CTD downward counter

With a rising flank on CD the counter of the function block CV is reduced by 1, as long as CV is greater than
-32768. If CV is less than or equal to 0, the output Q remains set to TRUE. Via LD the counter CV can be
set to the value saved in PV.

CD

LD

CV

Q

PV

Table 59 CTD downward counter

3.5.1.2

CTU upward counter

With a rising flank on CU, the counter of the function block CV is increased by 1. CV can count up to the
value 32767. As long as CV is greater than or equal to PV output Q remains set to TRUE. Via R the counter
CV can be reset to 0.

CU

R

CV

Q

PV

Table 60 CTU upward counter

VAR_INPUT

VAR_OUTPUT

Input

Explanation

Type

Output

Explanation

Type

CD

Counter input

BOOL

Q

TRUE, if CV <= 0

BOOL

LD

Lad starting value

BOOL

CV

Actual counter reading

INT

PV

Starting value

INT

VAR_INPUT

VAR_OUTPUT

Input

Explanation

Type

Output

Explanation

Type

CU

Counter input

BOOL

Q

TRUE, if CV >= PV

BOOL

R

Reset: counter reading

BOOL

CV

Actual counter reading

INT

PV

Max. counter value

INT