NORD Drivesystems BU0550 User Manual
Page 86
PLC logic for NORD SK 54xE frequency inverters
86
BU 0550 GB-0813
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P741
… [-01]
…
… [-23]
PZD bus out
(Process data Bus Out)
S
0 ... FFFF (hex)
This parameter provides information about the actual status word and the actual values that
are transferred via the bus system.
[-01] = Bus status word (P509)
Status word
[-02] = Actual bus value 1 (P543 [-01])
[-03] = Actual bus value 2 (P543 [-02])
[-04] = Actual bus value 3 (P543 [-03])
[-05] = Actual bus value 4 (P543 [-04])
[-06] = Actual bus value 5 (P543 [-05])
Actual values
[-07] = Resulting status OutBit P481
"Resulting status OutBit P481":The displayed
value depicts all Bus Out bit sources linked
with OR.
[-08] = Parameter data Out 1
[-09] = Parameter data Out 2
[-10] = Parameter data Out 3
[-11] = Parameter data Out 4
[-12] = Parameter data Out 5
Data during parameter transfer: Order label
(AK), Parameter number (PNU), Index (IND),
Parameter value (PWE 1/2).
[-13] = Actual value 1 of master function
(P502[-01])
[-14] = Actual value 2 of master function
(P502[-02])
[-15] = Actual value 3 of master function
(P502[-03])
[-16] = Actual value 4 of master function
(P502[-04])
[-17] = Actual value 5 of master function
(P502[-05])
Actual value data from master function value
(P502/P503).
[-18] = Status word PLC
Status word via the PLC.
[-19] = Actual value 1 PLC
[-20] = Actual value 2 PLC
[-21] = Actual value 3 PLC
[-22] = Actual value 4 PLC
[-23] = Actual value 5 PLC
Actual value data via the PLC.