4 Frequency inverter details

BU 0550 GB-0813

79

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P353

Bus status via PLC

(Bus status via PLC)

0 … 3

{ 0 }

This parameter decides whether the control word for the master function and the status word of
the frequency inverter are further processed by the PLC.

Setting:

0 = Off:

Control word for the master function (P503≠0) and the status word continue to be

processed by the PLC.

1 = Control word for master function via PLC: The control word for the master function

(P503≠ 0) is set by the PLC. For this, the control word must be redefined in the PLC by
means of process value "34_PLC_Busmaster_Control_word" (Section 4.2.2 ).

2 = Status word for Bus via PLC: The status word for the frequency inverter is set by the

PLC. For this, the control word must be redefined in the PLC by means of process
value "28_PLC_status_word" (Section 4.2.2 ).

3 = Control word and status word via PLC: See settings 1 and 2

P355

… [-01]

...

... [-10]

PLC Integer Setpoint

(PLC Integer Setpoint)

0x0000 … 0xFFFF

all { 0 }

Data can be exchanged with the PLC via this integer array. This data can be used by the
appropriate process variables in the PLC.

P356

… [-01]

… [-05]

PLC - DINT

– setpoint

(PLC - DINT

– setpoint)

0x0 … 0xFFFFFFFF

all { 0 }

Data can be exchanged with the PLC via this DINT array. This data can be used by the
appropriate process variables in the PLC.

P360

… [-01]

… [-05]

PLC display value

(PLC display value)

-

2.000,000 …

2.000,000

all { 0 }

Only used to display PLC data with a resolution of 0.001.

Via the corresponding process

variables, this parameter can be written by the PLC. The values are not saved!

P370

PLC Status

(PLC Status)

0 … 63

dec

ParameterBox:

0 … 3F

hex

Simple-/ ControlBox:

0 …. 11 1111

bin

PLC status

Bit 0 = P350 = 1

Bit 1 = PLC active

Bit 2 = Stop active

Bit 3 = Debug active

Bit 4 = PLC error, the PLC User errors 23.xx

are not displayed here

Bit 5 = PLC stopped, Single step or Breakpoint