beautypg.com

NORD Drivesystems BU0550 User Manual

Page 62

background image

PLC logic for NORD SK 54xE frequency inverters

62

BU 0550 GB-0813

Fig. 7 Schematic diagram of the Flying Saw synchronisation process

If the function is started, the slave frequency inverter accelerates to the speed of the master axis. The
acceleration ramp is specified via the "acceleration path" ACCELERATION. At low speeds the ramp is
flatter and at high master speeds the ramp for the slave frequency inverter is steeper. The acceleration path
is stated in revolutions (1000 = 1,000 rev.) if P553 is specified as the setpoint position. If the setpoint
position INC is used for P553, the acceleration path is specified in increments.

If the initiator is set in from of the position of the slave drive which is saved in ACCELERATION, the slave is
precisely synchronised to the triggering position of the master drive.

The FB must be switched on via the ENABLE input. The function can be started either via the digital input
(P420[-xx]=64, Start Flying Saw) or via EXECUTE. The frequency inverter then accelerates to the speed of
the master axis. Once synchronisation with the master axis has been achieved, the DONE output is
switched to 1.

Via the STOP input or the digital input function P420[-xx] = 77, Stop Flying Saw, the gear function is
switched off and the frequency inverter brakes to 0Hz and stops. Via the HOME input, the frequency inverter
is moved to the absolute position 0. The relevant assigned output is active after completion of the HOME or
STOP command. The gear function can be restarted via a new activation of EXECUTE or the digital input.
With the digital input function (P420[-xx] = 63, Switch off synchronisation) the gear function can be switched
off, with subsequent movement to the 0 position.

If the function is interrupted with the MC_Stop function, ABORT is set to 1. In case of error, ERROR is set to
1 and the error code is set in ERRORID. These three outputs are reset if ENABLE is set to 0.

Table 88 FB_FlyingSaw

VAR_INPUT

VAR_OUTPUT

Input

Explanation

Type

Output

Explanation

Type

ENABLE

Enable

BOOL

VALID

Specified setpoint frequency reached

BOOL

EXECUTE

Start of

synchronisation

BOOL

DONEHOME

Home run completed

STOP

Synchronisation

stopped

BOOL

DONESTOP

Stop command executed

HOME

Moves to position 0

BOOL

ABORT

Command aborted

BOOL

ACCELERATION

Acceleration path

(1rev. = 1.000)

DINT

ERROR

Error in FB

BOOL

ERRORID

Error code

INT

ERRORID

Explanation

0

No error

1000h

FI is not enabled

1200h

Position control not activated

Starting point of the Slave

Position of the initiator

Speed

Position

ACCELERATION

Removal of the initiator
to the starting position of
the Slave FI

Both drive units
running synchronously