NORD Drivesystems BU0550 User Manual
Page 53
3 AWL (Instruction List, IL)
BU 0550 GB-0813
53
3.5.2.2
MC_WriteParameter_16 / MC_WriteParameter_32
Writes a 16/32 Bit parameter into the frequency inverter, if EXECUTE changes from 0 to 1 (flank). The
parameter has been written if DONE is set to 1. For the duration of the reading process the BUSY output is
set to 1. In case of error, ERROR is set to 1 and the ERRORID contains the error code. The signals DONE,
ERROR, ERRORID remain set until EXECUTE changes back to 0. The writing process is not interrupted if
the EXECUTE signal changes to 0. It is only the DONE signal which only remains set for 1 PLC cycle.
If the RAMONLY input is set to 1, the settings will only be saved to the RAM. The changed settings will
therefore be lost if the FI is switched off.
Table 72 MC_WriteParameter16 / MC_WriteParameter32
VAR_INPUT
VAR_OUTPUT
Input
Explanation
Type
Output
Explanation
Type
EXECUTE
Enable
BOOL
DONE
Value is valid
BOOL
PARAMETER NUMBER
Parameter number
INT
BUSY
The writing process is active
BOOL
PARAMETER INDEX
Parameter index
INT
ERROR
Reading has failed
BOOL
VALUE
Value to be written
INT, DINT
ERRORID
Error code
INT
RAMONLY
Only save in RAM
ERRORID
Explanation
0
Invalid parameter number
1
Parameter value cannot be changed
2
Lower or upper value limit exceeded
3
Incorrect parameter index
4
No array
5
Invalid data type
6
Only resettable (only 0 may be written)
7
Description element cannot be changed
201
Invalid order element in the last order received
202
Internal response label cannot be depicted