3.5.2.3
MC_MoveVelocity
Sets the setpoint frequency for the frequency inverter if EXECUTE changes from 0 to 1 (flank). If the
frequency inverter has reached the setpoint frequency, INVELOCITY is set to 1. While the FI is accelerating
to the setpoint frequency the BUSY output is active. If EXECUTE has already been set to 0, INVELOCITY
is only set to 1 for one cycle.
If the process is interrupted (e.g. by another MC function module), COMMANDABORTED is set.
With a negative flank on EXECUTE all outputs are reset to 0.
VELOCITY is entered with scaling according to the following formula:
VELOCITY = ( Setpoint frequency (Hz) × 0x4000 ) / P105
Table 73 MC_MoveVelocity
VAR_INPUT
VAR_OUTPUT
Input
Explanation
Type
Output
Explanation
Type
EXECUTE
Enable
BOOL
INVELOCITY
Specified setpoint frequency
reached
BOOL
VELOCITY
Setpoint frequency
INT
BUSY
Setpoint frequency not yet reached
BOOL
COMMAND-
ABORTED
Command aborted
BOOL
ERROR
Error in FB
BOOL
ERRORID
Error code
INT
ERRORID
Explanation
0
No error
1000h
FI is not enabled
1100h
FI not in speed mode
1101h
No setpoint frequency parameterised (P553)