PLC logic for NORD SK 54xE frequency inverters
68
BU 0550 GB-0813
3.5.6.3
FB_DINTToPBox
This function module converts a DINT value into an ASCII string and copies it into the ParameterBox. The
output can be in decimal, binary or hexadecimal format. Selection is carried out via MODE. Via ROW and
COLUMN the starting position of the string is set in the P-Box display. The parameter LENGTH
communicates the length of the string in characters. In decimal MODE the parameter POINT inserts a
decimal point into the number to be displayed. POINT specifies how many characters are to the right of the
decimal point. The function POINT is switched off with the setting 0.
If the number contains more characters than the length allows and no decimal point is set, the overflow is
indicated by the character "#". If there is a decimal point in the number, all numbers behind the decimal point
by be omitted if required. In hexadecimal and binary MODE the lowest value bits are displayed if the set
length is too short.
As long as ENABLE is set to 1, all changes at the inputs are adopted immediately.
If DONE switches to 1, the string has been transferred correctly.
In case of error, ERROR is set to 1. In this case, DONE is 0. The corresponding error code in the ERRORID
applies.
DONE, ERROR and ERRORID are reset with a negative flank on ENABLE.
Examples:
Setting
Number to be displayed
P-Box display
Length = 5
12345
12345
Point = 0
Length = 5
-12345
#####
Point = 0
Length = 10
123456789
123456,789
Point = 3
Length = 8
123456789
123456,7
Point = 3
Table 93 FB_DINTToPBox
VAR_INPUT
VAR_OUTPUT
Input
Explanation
Type
Output
Explanation
Type
ENABLE
Transfer of string
BOOL
DONE
String transferred
BOOL
MODE
Display format
0 = Decimal
1 = Binary
2 = Hexadecimal
Value range = 0 to 2
BYTE
ERROR
Error in FB
BOOL
ROW
Row of the display
Value range = 0 to 3
BYTE
ERRORID
Error code
INT
COLUMN
Column of the display
Value range = 0 to 19
BYTE
POINT
Position of the decimal point
Value range = 0 to 10
0 = Function is disabled
BYTE
LENGTH
Output length
Value range = 1 to 11
BYTE
VALUE
Number to be output
DINT
ERRORID
Explanation
0
No error
1500h
String overwrites the memory area of the P-Box array
1501h
Value range exceeded at LINE input
1502h
Value range exceeded at ROW input
1504h
Value range exceeded at POINT input
1505h
Value range exceeded at LENGTH input
1506h
Value range exceeded at MODE input