4 extra functions – NORD Drivesystems BU0550 User Manual
Page 83
4 Frequency inverter details
BU 0550 GB-0813
83
4.1.4
Extra functions
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P502
… [-01]
…
… [-05]
Value master function
(Master function value)
S
P
0 … 58
all { 0 }
Selection of up to 5 master values:
[-01] = Master value 1
…
[-05] = Master value 5
Setting:
…
53 = PLC_status_word
54 = PLC_act_val1
55 = PLC_act_val2
56 = PLC_act_val3
57 = PLC_act_val4
58 = PLC_act_val5
P503
Leading func. output
(Master function output)
S
0 ... 5
{ 0 }
To use the Master function output, the inverter controller source must be selected in P509.
The master value to be transmitted is determined via the BUS interface in parameter P502.
0 = Off
1 = USS
2 = CAN (up to 250kBaud)
3 = CANopen
4 = System bus active
5 = CANopen+Sys.bus act.
P509
Source Control word
(Control word source)
0 ... 10
{ 0 }
Selection of the interface via which the FI is controlled (for details see BU0500). Also note
parameter (P350).
0 = Control terminals or keyboard
1 = Control terminals
2 = USS (or Modbus RTU SK 540E and
above)
3 = CAN
4 = Profibus
5 = InterBus
6 = CANopen
7 = DeviceNet
8 = Ethernet TU
9 = CAN Broadcast
10 = CANopen Broadcast
P510
[-01]
[-02]
Source setpoints
(Setpoints source)
S
0 ... 10
{ all 0 }
Selection of the setpoints to be parameterised (For details see BU0500). Also note
parameters (P350) and (P351).
[-01] = Main setpoint source
[-02] = Auxiliary setpoint source
0 = Auto
1 = Control terminals
2 = USS (or Modbus RTU SK 540E and above)
3 = CAN
4 = Profibus
5 = InterBus
6 = CANopen
7 = DeviceNet
8 = Ethernet TU
9 = CAN Broadcast
10 = CANopen Broadcast