P6700, p8700 & p4700 controllers, Serial communications parameters, Bit parameters – West Control Solutions 8700+ User Manual
Page 98: Word parameters
1
/
4
-DIN,
1
/
8
-DIN &
1
/
16
- DIN Controllers & Indicators - Product Manual
59305, Issue 7
– March 2014
P6700, P8700 & P4700 Model Group
Page 93
P6700, P8700 & P4700 Controllers
– Serial Communications Parameters
The Modbus parameter addresses, and the possible ASCII message types and parameters
indents for the P6700, P8700 & P4700 are detailed below. RO indicates a parameter is read
only, R/W indicates it can also be written to. Communications writes will not implemented if
the Communications Write Parameter is disabled. Refer to the Modbus and ASCII
Communications sections of this manual for details of the protocols used.
Bit Parameters
Bit parameters are not applicable to the ASCII protocol.
Table 24. P6700, P8700 & P4700 Communications - Bit Parameters
Parameter
Modbus
Parameter No.
Notes
1
RO
1 = Write Enabled, 0 = Write Disabled. A negative
acknowledgement (exception code 3) is sent to write
commands if communications writes are disabled
2
RO
1 = Low Limit, 0 = High Limit
3
R/W
1 = Reset Latched Relays. A read returns the values 0
4
RO
1 =In Exceed Condition, 0 = Not in Exceed Condition
Alarm 1 Status
5
RO
1 = Active, 0 = Inactive
Alarm 2 Status
6
RO
1 = Active, 0 = Inactive
7
RO
1 = Relay latched, 0 = Relay not latched
8
RO
1 = Active, 0 = Inactive
To set the bit value to 1 write FF, to set the bit value to 0 write 00. Refer to Function Code 05 in the
Modbus Communications section.
Word Parameters
Table 25. P6700, P8700 & P4700 Communications - Word Parameters
Parameter
Modbus
Parameter No.
ASCII Ident &
Message Types
Notes
1
RO
M
Type 2
RO
Current value of PV.
If under-range = 62976 (?>5 ASCII)
If over-range = 63232 (?>0 ASCII)
If Sensor break = 63488 (ASCII = n/a)
2
R/W
S
Type 2, 3/4
R/W
Value of the Limit Setpoint.
Hold Value
3
R/W
A
Type 2
RO
Highest PV value (High Limit Action)
or Lowest PV value (Low Limit Action)
since this parameter was last reset.
Modbus: Write any value to reset
ASCII: See Controller Command
00160 for reset.
Deviation
4
RO
V
Type 2
RO
Difference between Process Variable
and Limit Setpoint (value = PV-Limit
SP)