P6700, P8700 & P4700 Controllers

– Serial Communications Parameters

The Modbus parameter addresses, and the possible ASCII message types and parameters
indents for the P6700, P8700 & P4700 are detailed below. RO indicates a parameter is read
only, R/W indicates it can also be written to. Communications writes will not implemented if
the Communications Write Parameter is disabled. Refer to the Modbus and ASCII
Communications sections of this manual for details of the protocols used.

Bit Parameters

Bit parameters are not applicable to the ASCII protocol.

Table 24. P6700, P8700 & P4700 Communications - Bit Parameters

Parameter

Modbus

Parameter No.

Notes

Communication
Write Status

1

RO

1 = Write Enabled, 0 = Write Disabled. A negative
acknowledgement (exception code 3) is sent to write
commands if communications writes are disabled

Limit Action

2

RO

1 = Low Limit, 0 = High Limit

Reset Limit Relay

3

R/W

1 = Reset Latched Relays. A read returns the values 0

Limit Status

4

RO

1 =In Exceed Condition, 0 = Not in Exceed Condition

Alarm 1 Status

5

RO

1 = Active, 0 = Inactive

Alarm 2 Status

6

RO

1 = Active, 0 = Inactive

Limit Output Status

7

RO

1 = Relay latched, 0 = Relay not latched

Annunciator Output
Status

8

RO

1 = Active, 0 = Inactive

To set the bit value to 1 write FF, to set the bit value to 0 write 00. Refer to Function Code 05 in the
Modbus Communications section.

Word Parameters

Table 25. P6700, P8700 & P4700 Communications - Word Parameters

Parameter

Modbus

Parameter No.

ASCII Ident &

Message Types

Notes

Process Variable

1

RO

M

Type 2

RO

Current value of PV.

If under-range = 62976 (5 ASCII)

If over-range = 63232 (0 ASCII)

If Sensor break = 63488 (ASCII = n/a)

Limit Setpoint

2

R/W

S

Type 2, 3/4

R/W

Value of the Limit Setpoint.

Hold Value

3

R/W

A

Type 2

RO

Highest PV value (High Limit Action)
or Lowest PV value (Low Limit Action)
since this parameter was last reset.
Modbus: Write any value to reset
ASCII: See Controller Command
00160 for reset.

Deviation

4

RO

V

Type 2

RO

Difference between Process Variable
and Limit Setpoint (value = PV-Limit
SP)