beautypg.com

Option slot 2 - dual relay output module, Po2-c21, Linear ma/v dc – West Control Solutions 8700+ User Manual

Page 35: Po2-w09, Dual relay, P o2- c10, Relay

background image

1

/

4

-DIN,

1

/

8

-DIN &

1

/

16

- DIN Controllers & Indicators - Product Manual


Page 30

Connections

59305, Issue 7

– March 2014

Option Slot 2 - Dual Relay Output Module

If option slot 2 is fitted with a dual relay output module, make connections as illustrated. This
module has two independent relays, which share a common connection terminal. The
contacts are rated at 2 amp resistive 240 VAC. (120V max for direct Valve Motor control).

1

/

16

DIN

1

/

4

DIN &

1

/

8

DIN

Figure 25.

Option Slot 2 - Dual Relay Module

WARNING:

THIS MODULE MUST NOT BE FITTED INTO OPTION SLOT 3 ON

1

/

16

DIN INSTRUMENTS.

Option Slot 2 - Linear Voltage or mADC Output module

If option slot 2 is fitted with a DC linear output module, make connections as illustrated.

1

/

16

DIN

1

/

4

DIN &

1

/

8

DIN

Figure 26.

Option Slot 2 - Linear Voltage & mADC module

22

23

_

24

+

13

14

+

15

_

22

23

N/O OUTPUT 4

COMMON

24

N/O OUTPUT 2

13

14

N/O OUTPUT 2

COMMON

15

N/O OUTPUT 4

This manual is related to the following products: