Specifications
Page 165
Triac:
Operating Voltage Range:
20 to 280Vrms @47 to 63Hz. (140V
max when directly driving motorised
valves).
Current Rating:
0.01 to 1A (full cycle rms on-state @
25
C); derates linearly above 40
C to
0.5A @ 80
C.
Max. Non-repetitive Surge
Current (16.6ms):
25A peak.
Min. OFF-State dv/dt @ Rated
Voltage:
500V/
s.
Max. OFF-State leakage @
Rated Voltage:
1mA rms.
Max. ON-State Voltage Drop @
Rated Current:
1.5V peak.
Repetitive Peak OFF-state
Voltage, Vdrm:
600V minimum.
Isolation:
Reinforced safety isolation from inputs
and other outputs.
Linear DC:
Resolution:
Eight bits in 250mS
(10 bits in 1 second typical, >10 bits in
>1 second typical).
Update Rate:
Every control algorithm execution.
Ranges:
0 to 10V
0 to 5V
2 to 10V
0 to 20mA
4 to 20mA
(default)
Load Impedance:
0 to 20mA & 4 to 20mA:
500
Ω maximum.
0 to 5V, 0 to 10V & 2 to 10V:
500Ω minimum.
Short circuit protected.
Accuracy:
0.25% (mA @ 250
Ω, V @ 2kΩ).
Degrades linearly to
0.5% for
increasing burden (to specification
limits).
When used as control output:
For 4 to 20mA and 2 to 10V a 2%
over/underdrive is applied (3.68 to
20.32mA and 1.84 to 10.16V).
Isolation:
Reinforced safety isolation from inputs
and other outputs.
Use as 0 to 10VDC transmitter
power supply*
Indicators only.
Adjustable, 0.0 to 10.0V (regulated)
output into 500
minimum.
Transmitter Power
Supply:
*
see Linear output
spec for 0-10V PSU
Power Rating
19 to 28VDC (24V nominal) into 910
Ω
minimum resistance.
Isolation:
Reinforced safety isolation from inputs
and other outputs.