beautypg.com

West Control Solutions 8700+ User Manual

Page 170

background image

1

/

4

-DIN,

1

/

8

-DIN &

1

/

16

- DIN Controllers & Indicators - Product Manual


59305, Issue 7

– March 2014

Specifications

Page 165

Triac:

Operating Voltage Range:

20 to 280Vrms @47 to 63Hz. (140V
max when directly driving motorised
valves).

Current Rating:

0.01 to 1A (full cycle rms on-state @
25

C); derates linearly above 40

C to

0.5A @ 80

C.

Max. Non-repetitive Surge
Current (16.6ms):

25A peak.

Min. OFF-State dv/dt @ Rated
Voltage:

500V/

s.

Max. OFF-State leakage @
Rated Voltage:

1mA rms.

Max. ON-State Voltage Drop @
Rated Current:

1.5V peak.

Repetitive Peak OFF-state
Voltage, Vdrm:

600V minimum.

Isolation:

Reinforced safety isolation from inputs
and other outputs.

Linear DC:

Resolution:

Eight bits in 250mS
(10 bits in 1 second typical, >10 bits in
>1 second typical).

Update Rate:

Every control algorithm execution.

Ranges:

0 to 10V
0 to 5V
2 to 10V

0 to 20mA
4 to 20mA
(default)

Load Impedance:

0 to 20mA & 4 to 20mA:
500

Ω maximum.

0 to 5V, 0 to 10V & 2 to 10V:
500Ω minimum.
Short circuit protected.

Accuracy:

0.25% (mA @ 250

Ω, V @ 2kΩ).

Degrades linearly to

0.5% for

increasing burden (to specification
limits).

When used as control output:

For 4 to 20mA and 2 to 10V a 2%
over/underdrive is applied (3.68 to
20.32mA and 1.84 to 10.16V).

Isolation:

Reinforced safety isolation from inputs
and other outputs.

Use as 0 to 10VDC transmitter
power supply*
Indicators only.

Adjustable, 0.0 to 10.0V (regulated)
output into 500

minimum.

Transmitter Power
Supply:

*

see Linear output

spec for 0-10V PSU

Power Rating

19 to 28VDC (24V nominal) into 910

Ω

minimum resistance.

Isolation:

Reinforced safety isolation from inputs
and other outputs.

This manual is related to the following products: