Panel-mounting – West Control Solutions 8700+ User Manual
Page 17
1
/
4
-DIN,
1
/
8
-DIN &
1
/
16
- DIN Controllers & Indicators - Product Manual
Page 12
Installation
59305, Issue 7
– March 2014
The mounting panel must be rigid and may be up to 6.0mm (0.25 inches) thick. The cut-outs
required for the instruments are shown below.
Figure 2. Panel cut-out sizes
Panel-Mounting
CAUTION:
Ensure the inside of the panel is with the instruments operating temperature and
that there is adequate air flow to prevent overheating.
Mounting
Panel
Instrument
Housing
Ratchets
Gasket
1. Insert instrument into the panel
cut-out.
2. Hold front bezel firmly (without
pressing on display area), and re-
fit mounting clamp. Push clamp
forward, using a tool if necessary,
until gasket is compressed
and instrument held firmly in
position.
Figure 3. Panel-Mounting the instrument
CAUTION:
For an effective IP66 seal against dust and moisture, ensure gasket is well
compressed against the panel, with the 4 tongues located in the same ratchet slot.
1
/
16
DIN
45mm
+0.5
–0.0
1
/
8
DIN
92mm
+0.5
–0.0
(45mm for
indicator)
1
/
4
DIN
92mm
+0.5
–0.0
92mm
+0.5
–0.0
45mm +0.5
–0.0
(92mm for indicator)
45mm
+0.5
–0.0