– March 2014

The mounting panel must be rigid and may be up to 6.0mm (0.25 inches) thick. The cut-outs
required for the instruments are shown below.

Figure 2. Panel cut-out sizes

Panel-Mounting

CAUTION:

Ensure the inside of the panel is with the instruments operating temperature and
that there is adequate air flow to prevent overheating.

Mounting

Panel

Instrument

Housing

Ratchets


Gasket


1. Insert instrument into the panel
cut-out.

2. Hold front bezel firmly (without
pressing on display area
), and re-
fit mounting clamp. Push clamp
forward, using a tool if necessary,
until gasket is compressed
and instrument held firmly in
position.

Figure 3. Panel-Mounting the instrument

CAUTION:

For an effective IP66 seal against dust and moisture, ensure gasket is well
compressed against the panel, with the 4 tongues located in the same ratchet slot.

1

/

16

DIN

45mm

+0.5

–0.0

1

/

8

DIN

92mm

+0.5

–0.0

(45mm for

indicator)

1

/

4

DIN

92mm

+0.5

–0.0

92mm

+0.5

–0.0

45mm +0.5

–0.0

(92mm for indicator)

45mm

+0.5

–0.0

This manual is related to the following products: