West Control Solutions 8700+ User Manual
Page 121
1
/
4
-DIN,
1
/
8
-DIN &
1
/
16
- DIN Controllers & Indicators - Product Manual
Page 116
P6010 & P8010 Model Group
59305, Issue 7
– March 2014
Parameter
Modbus
Parameter No.
ASCII Ident &
Message Types
Notes
Date of
manufacture
126
RO
Manufacturing date code as an
encoded binary number.
E.g. 0403 for April 2003 is returned as
193hex
Product Revision
Level
129
RO
Low Byte
Alpha part of PRL.
E.g. A = 01hex
High Byte
Numeric part of PRL.
E.g. 13 = 0Dhex
Firmware Version
130
RO
Bits
Meaning
0 - 4
Revision number (1,2...)
5 - 9
Alpha version (A=0,
B=1...)
10 - 15
Numeric version
(starting from 121 = 0)
Input status
133
RO
Input status. Read Only.
Bit 0: Sensor break flag
Bit 1: Under-range flag
Bit 2: Over-range flag
Tare Enable
2111
R/W
0 = Disabled, 1 = Enabled
Tare Activate
2112
RO
Write any value to activate.
Option Slot 1
Re-transmit output
Maximum
2214
R/W
Maximum scale value for retransmit
output in slot 1, 1999 to 9999.
Option Slot 1
Re-transmit output
Minimum
2215
R/W
Minimum scale value for retransmit
output in slot 1, 1999 to 9999.
Option Slot 2
Re-transmit output
Maximum
2224
R/W
Maximum scale value for retransmit
output in slot 2, 1999 to 9999.
Option Slot 2
Re-transmit output
Minimum
2225
R/W
Minimum scale value for retransmit
output in slot 2, 1999 to 9999.
Option Slot 3
Re-transmit output
Maximum
2234
R/W
Maximum scale value for retransmit
output in slot 3, 1999 to 9999.
Option Slot 3
Re-transmit output
Minimum
2235
R/W
Minimum scale value for retransmit
output in slot 3, 1999 to 9999.
Note:
Some of the parameters that do not apply to a particular configuration will accept reads
and writes (e.g. attempting to scale a Linear output which has not been fitted). Read only
parameters will return an exception if an attempt is made to write values to them.