beautypg.com

Appendix 2 - specification, Universal input, General input specifications – West Control Solutions 8700+ User Manual

Page 165: Thermocouple, Thermocouple ranges available, Specification, 17 appendix 2 - specification

background image

1

/

4

-DIN,

1

/

8

-DIN &

1

/

16

- DIN Controllers & Indicators - Product Manual


Page 160

Specifications

59305, Issue 7

– March 2014

17 Appendix 2 - Specification

Universal Input

General Input Specifications

Input Sample Rate:

Four samples/second.

Digital Input Filter
time constant

0.0 (OFF), 0.5 to 100.0 seconds in 0.5 second increments.

Input Resolution:

14 bits approximately.
Always four times better than display resolution.

Input Impedance:

10V DC:

47KΩ

20mA DC:

Other ranges:

Greater than 10M

resistive

Isolation:

Isolated from all outputs (except SSR driver). If single relay outputs are
connected to a hazardous voltage source, and the universal input is
connected to operator accessible circuits, supplementary insulation or
input grounding is required.

PV Offset:

Adjustable

input span.

PV Display:

Displays process variable up to 5% over and 5% under span.

Thermocouple

Thermocouple Ranges Available

Sensor
Type

Range Min
in

C

Range Max
in

C

Range Min
in

F

Range Max
in

F

Resolution

J (default)

-200

1200

-328

2192

J

-128.8

537.7

-199.9

999.9

0.1°

T

-240

400

-400

752

T

-128.8

400.0

-199.9

752.0

0.1°

K

-240

1373

-400

2503

K

-128.8

537.7

-199.9

999.9

0.1°

L

0

762

32

1403

L

0.0

537.7

32.0

999.9

0.1°

N

0

1399

32

2551

B

100

1824

211

3315

R

0

1759

32

3198

S

0

1762

32

3204

C

0

2320

32

4208

PtRh20%:
PtRh40%

0

1850

32

3362

Note:

Defaults to °F for USA units. Defaults to °C for non-USA units.
The Configuration Mode parameters, Scale Range Upper Limit and Scale Range Lower
Limit, can be used to restrict range.