West Control Solutions 8700+ User Manual
Page 56
1
/
4
-DIN,
1
/
8
-DIN &
1
/
16
- DIN Controllers & Indicators - Product Manual
59305, Issue 7
– March 2014
P6100, P8100 & P4100 Model Group
Page 51
Table 12. P6100, P8100 & P4100 Set Up Mode Parameters
Parameter
Lower
Display
Upper Display
Adjustment Range
Default
Value
When
Visible
OFF, 0.5 to 100.0 secs in
0.5 sec increments
.
Always
Span of controller
Always
Primary Power
The current Primary
Output Power. Read Only.
N/A
Always
Secondary Power
The current Secondary
Output power. Read Only.
N/A
=
Primary Output
Proportional Band
0.0% (ON/OFF control)
and 0.5% to 999.9% of
input span.
.
Always
Secondary Output
Proportional Band
0.0% (ON/OFF control)
and 0.5% to 999.9% of
input span.
.
=
Automatic Reset
(Integral Time
Constant)
0.01 to 99.59 (1 sec to 99
mins 59 secs) and OFF
.
is not
.
Rate (Derivative Time
Constant)
0.00 to 99.59 (OFF to 99
mins 59 secs)
.
is not
.
-20% to +20% of the sum
of the Primary and
Secondary Proportional
Bands
is not
.
0% to 100% (-100% to
100% if
=
)
is not
.
Primary Output
ON/OFF Differential
0.1% to 10.0% of input
span (enter in % span)
.
=
.
Secondary Output
ON/OFF Differential
0.1% to 10.0% of input
span (enter in % span)
.
=
.
Primary and Secondary
Output ON/OFF
Differential
0.1% to 10.0% of input
span (enter in % span)
.
and
=
.
Current Setpoint value to
Scale Range Maximum
Range
Max.
Always
Scale Range Minimum to
current Setpoint value
Range Min Always
Primary (Heat) Output
Upper Power Limit
0% to 100% of full power
is not
.
0.5, 1, 2, 4, 8, 16, 32, 64,
128, 256 or 512 secs.
Not applicable to linear
outputs
=
or