P6700, P8700 & P4700 Model Group

Page 95

Parameter

Modbus

Parameter No.

ASCII Ident &

Message Types

Notes

Controller
Commands

Z

Type 3/4

R/W

The Type 3 {DATA} field must be one
of three five-digit numbers:
00150 = Reset Limit Outputs
00160 = Reset Hold Value
00170 = Reset Exceed Time value
The response contains the same
{DATA}. A negative acknowledgement
will be returned if Reset in not
possible or already implemented.

Controller Status

L

Type 2

RO

Bits

Meaning

0

Alarm 1 status:
0 = Activated, 1 = Safe

1

Alarm 2 status:
0 = Activated, 1 = Safe

2

Not used

3

Change Indicator:
0 = No changes, since
Controller Status was
last read.
1 = A parameter other
than Controller Status
or PV has changed

4

Comms write status:
0 = Disabled
1 = Enabled

5

Not used

6

Not used

7

Not used

8

Not used

9

Limit status:
0 = Not Exceeded, 1 =
Exceeded

10

Limit Relay Status:
0 = safe, 1 = Latched
Off

11

Limit Action:
0 = Low Limit, 1 = High
Limit

12

Annunciator status:
0 = inactive, 1 = Active

Scan Table

]

Type 2

RO

Reads back main process values.
Response is: L{N}25aaaaabbbbb
cccccdddddeeeeeA* where:
aaaaa = Limit Setpoint value
bbbbb = Process Variable value
ccccc = Hold value
ddddd = Exceeded Time value
eeeee = Controller Status (see above)

Equipment ID

122

RO

The four digit model number 6700