West Control Solutions 8700+ User Manual
Page 100

1
/
4
-DIN,
1
/
8
-DIN &
1
/
16
- DIN Controllers & Indicators - Product Manual
59305, Issue 7
– March 2014
P6700, P8700 & P4700 Model Group
Page 95
Parameter
Modbus
Parameter No.
ASCII Ident &
Message Types
Notes
Controller
Commands
Z
Type 3/4
R/W
The Type 3 {DATA} field must be one
of three five-digit numbers:
00150 = Reset Limit Outputs
00160 = Reset Hold Value
00170 = Reset Exceed Time value
The response contains the same
{DATA}. A negative acknowledgement
will be returned if Reset in not
possible or already implemented.
Controller Status
L
Type 2
RO
Bits
Meaning
0
Alarm 1 status:
0 = Activated, 1 = Safe
1
Alarm 2 status:
0 = Activated, 1 = Safe
2
Not used
3
Change Indicator:
0 = No changes, since
Controller Status was
last read.
1 = A parameter other
than Controller Status
or PV has changed
4
Comms write status:
0 = Disabled
1 = Enabled
5
Not used
6
Not used
7
Not used
8
Not used
9
Limit status:
0 = Not Exceeded, 1 =
Exceeded
10
Limit Relay Status:
0 = safe, 1 = Latched
Off
11
Limit Action:
0 = Low Limit, 1 = High
Limit
12
Annunciator status:
0 = inactive, 1 = Active
Scan Table
]
Type 2
RO
Reads back main process values.
Response is: L{N}25aaaaabbbbb
cccccdddddeeeeeA* where:
aaaaa = Limit Setpoint value
bbbbb = Process Variable value
ccccc = Hold value
ddddd = Exceeded Time value
eeeee = Controller Status (see above)
Equipment ID
122
RO
The four digit model number 6700