West Control Solutions 8700+ User Manual
Page 86
![background image](/manuals/370832/86/background.png)
1
/
4
-DIN,
1
/
8
-DIN &
1
/
16
- DIN Controllers & Indicators - Product Manual
59305, Issue 7
– March 2014
P6170, P8170 & P4170 Model Group
Page 81
Parameter
Modbus
Parameter No.
Notes
9
R/W
Derivative Time Constant value.
Read only if Self-Tuning.
Adjustable 0 to 5999
10
R/W
Adjustable 5 to 300 seconds
11
R/W
Lower limit of scaled input range
12
R/W
Upper limit of scaled input range
13
R/W
Alarm 1 active at this level
14
R/W
Alarm 2 active at this level
Decimal Point
Position
18
R/W
0 = xxxx
1 = xxx.x
2 = xx.xx
3 = x.xxx
Read only if not Linear Input.
19
R/W
Adjustable 0 to (Motor Travel Time/10) in 0.1 sec
increments
Actual Setpoint
21
RO
Current (ramping) value of selected setpoint.
22
R/W
Maximum setpoint value. Current SP to Input Range
Maximum
23
R/W
Minimum setpoint value. Current SP to Input Range
Minimum
24
R/W
0 = 0ff, 1 to 9999 increments / hour. Dec Point position
as for input range.
25
R/W
0 to 100 seconds
Process Value
Offset
26
R/W
Modified PV = Actual PV + PV Offset. Limited by Scale
Range Maximum and Scale Range Minimum.
Re-transmit Output
Maximum
27
R/W
Maximum scale value for retransmit output, 1999 to
9999. This parameter applies to the first re-transmit
output fitted (see also parameters 2214, 2224 & 2234).
Re-transmit Output
Minimum
28
R/W
Minimum scale value for retransmit output, 1999 to 9999.
This parameter applies to the first re-transmit output fitted
(see also parameters 2215, 2225 & 2235).
Setpoint 2
29
R/W
Value of Setpoint 2
Remote Setpoint
30
RO
Value of Remote Setpoint.
Returns 0FFFFhex if RSP not fitted.
Remote Setpoint
Offset
31
R/W
Modified RSP = Actual RSP + RSP Offset. Limited by
Scale Range Maximum and Scale Range Minimum.
32
R/W
0 to 100% of span
33
R/W
0 to 100% of span
Setpoint 1
34
R/W
Value of Setpoint 1
Setpoint Select
35
R/W
Shows which is the currently selected active setpoint. If a
digital input has been configured for Setpoint Select, it
will take priority over this parameter
1 = SP1 or LSP, 2 = SP2, 100hex = RSP
Equipment ID
122
RO