Output specifications, Output module types, Specifications of output types – West Control Solutions 8700+ User Manual
Page 169
1
/
4
-DIN,
1
/
8
-DIN &
1
/
16
- DIN Controllers & Indicators - Product Manual
Page 164
Specifications
59305, Issue 7
– March 2014
Output Specifications
Output Module Types
Option Slot 1 Module Options:
Relay, SSR drive, Triac or DC linear.
Limit Controllers have a fixed Latching Relay only.
Option Slot 2 Module Options:
Relay, Dual Relay, SSR drive, Triac or DC linear.
Dual Relay option on some models only.
Option Slot 3 Module Options:
Relay, Dual Relay, SSR drive, DC Linear or Transmitter
PSU. Dual Relay option on some models only.
Specifications of Output Types
Single Relay:
Contact Type:
Single pole double throw (SPDT).
Control Rating:
2A resistive at 240V AC (120V when
directly driving motorised valves).
Limit Controller has a fixed 5A latching
relay, in Option Slot 1.
Alarm Rating:
2A resistive at 240V AC
Control/Alarm Lifetime:
>500,000 operations at rated
voltage/current.
Limit Output Lifetime:
>100,000 operations at rated
voltage/current.
Isolation:
Basic Isolation from universal input
and SSR outputs.
Dual Relay:
Contact Type:
2 x Single pole single throw (SPST)
with shared common.
Control Rating:
2A resistive at 240V AC (120V when
directly driving motorised valves).
Control/Alarm Lifetime:
>200,000 operations at rated
voltage/current.
Isolation:
Reinforced safety isolation from inputs
and other outputs.
SSR Driver:
Drive Capability:
10V minimum at up to 20mA load.
Isolation:
Not isolated from universal input or
other SSR driver outputs.