beautypg.com

Derivative, Type: controller parameter, Deviation alarm 1 value type – West Control Solutions 8700+ User Manual

Page 144: Type: general parameter, Deviation alarm 2 value, Differential (on-off hysteresis), Direct/reverse action of control outputs, Type: controller definition, Display strategy, Elapsed time

background image

1

/

4

-DIN,

1

/

8

-DIN &

1

/

16

- DIN Controllers & Indicators - Product Manual


59305, Issue 7

– March 2014

Glossary

Page 139

Derivative

Type: Controller Parameter

Refer to Rate.

Deviation Alarm 1 Value Type

Type: General Parameter

This is applicable only if Alarm 1 is selected to be Deviation Alarm. A positive value
(Deviation High) sets the alarm point above the current actual setpoint, a negative value
(Deviation Low) sets it below. If the process variable deviates from the setpoint by a margin
greater than this value, alarm 1 becomes active.
Display code =



, Default value = 5.

Also refer to Alarm Operation and Deviation Alarm 2 Value.

Deviation Alarm 2 Value

Type: General Parameter

Applicable only if Alarm 2 is selected as a Deviation Alarm. It is similar to Deviation Alarm 1
Value.
Display code =



. Default value = 5.

Also refer to Alarm Operation and Deviation Alarm 1 Value.

Differential (On-Off Hysteresis)

Type: Controller Parameter

A switching differential used when one or both control outputs have been set to On-Off. This
parameter is adjustable within the range 0.1% to 10.0% of input span; the default value is
0.5%. The differential band is centred about the setpoint.
Relay chatter can be eliminated by proper adjustment of this parameter. Too large a value for
this parameter will increase amplitude of oscillation in this process variable.
Display code =



for primary only differential,



for secondary only differential &



for primary and secondary differential.

Also refer to Input Span and On-Off Control.

Direct/Reverse Action of Control Outputs

Type: Controller Definition

Direct action is typically used with cooling applications; On-Off direct outputs will turn on
when the process variable exceeds setpoint. Proportional direct outputs will increase the
percentage of output as the process value increases within the proportional band. Reverse
action is typically used with heating applications; On-Off reverse outputs will turn off when
the process variable exceeds setpoint. Proportional reverse outputs will decrease the
percentage of output as the process value increases within the proportional band. The
Secondary Output will be direct whenever the Primary Output is selected as reverse. The
Secondary Output will be reverse whenever the Primary Output is selected as direct.
Also refer to Control Type, On-Off Control, PID, Primary Proportional Band and Secondary
Proportional Band

Display Strategy

Type: General Parameter

Alters the parameters displayed in normal operator mode. For example a controller could
display PV + SP, PV + adjustable SP, PV + Ramping SP, PV only or SP only. Display
strategy 6 will allow read only access to the setpoint values in Operator Mode, Setup Mode
must then be entered to change the setpoint.
Display code =



Also refer to Process Variable, Setpoint and Setpoint Ramping.

Elapsed Time

Type: Indicator Definition

The total accumulated time that Alarm 1 has been active on an Indicator since this parameter
was last reset. This does not include the time when the alarm condition has cleared. The
Elapsed Time is not affected by the Alarm 2 and Alarm 3 status.
Also refer to Alarm Operation, Exceed Time and Indicator.

This manual is related to the following products: