Changing parameter values – West Control Solutions 8700+ User Manual
Page 89
![background image](/manuals/370832/89/background.png)
1
/
4
-DIN,
1
/
8
-DIN &
1
/
16
- DIN Controllers & Indicators - Product Manual
Page 84
P6700, P8700& P4700 Model Group
59305, Issue 7
– March 2014
Changing Parameter Values
Press to navigate to the required parameter, then press or to set the
value as required.
When a value is changed, the display will flash to indicate that confirmation of the change is
required. The value will revert back if not confirmed within 10 seconds.
Press to accept the change.
Or
Press to reject the change and to move onto the next parameter.
Hold down and press to return to Select Mode.
Note:
If there is no key activity for 2 minutes, the instrument returns to the operator mode.
Table 21. P6700, P8700 & P4700 Configuration Mode Parameters
Parameter
Lower
Display
Upper
Display
Description
Default
Value
When
Visible
Input type and
Range
B type: 100 to 1824 ºC
for Europe
for USA
Always
B type: 211 to 3315 ºF
C type: 0 to 2320 ºC
C type: 32 to 4208 ºF
J type: -200 to 1200 ºC
J type: -328 to 2192 ºF
J type: -128.8 to 537.7 ºC
with decimal point
J type: -199.9 to 999.9 ºF
with decimal point
K type: -240 to 1373 ºC
K type: -400 to 2503 ºF
K type: -128.8 to 537.7 ºC
with decimal point
K type: -199.9 to 999.9 ºF
with decimal point
L type: 0 to 762 ºC
L type: 32 to 1403 ºF
L type: 0.0 to 537.7 ºC
with decimal point
L type: 32.0 to 999.9 ºF
with decimal point