beautypg.com

Thermocouple performance, Resistance temperature detector (rtd), Rtd ranges available – West Control Solutions 8700+ User Manual

Page 166

background image

1

/

4

-DIN,

1

/

8

-DIN &

1

/

16

- DIN Controllers & Indicators - Product Manual


59305, Issue 7

– March 2014

Specifications

Page 161

Thermocouple Performance

Calibration:

Complies with BS4937, NBS125 and IEC584.

Measurement
Accuracy:

0.1% of full range span

1LSD.

NOTE: Reduced performance for B Thermocouple from 100 to 600°C.
NOTE: PtRh 20% vs PtRh 40% Thermocouple accuracy is 0.25% and has
reduced performance below 800°C.

Linearisation
Accuracy:

Better than

0.2

C any point, for 0.1° resolution ranges (

0.05

C typical).

Better than

0.5

C any point, for 1° resolution ranges.

Cold Junction
Compensation:

Better than

0.7

C under reference conditions.

Better than

1

C under operating conditions.

Temperature
Stability:

0.01% of span/

C change in ambient temperature.

Supply Voltage
Influence:

Negligible.

Relative Humidity
Influence:

Negligible.

Sensor Resistance
Influence:

Thermocouple 100Ω: <0.1% of span error.
Thermocouple 1000Ω: <0.5% of span error.

Sensor Break
Protection:

Break detected within two seconds. Process Control outputs turn OFF
(0% power); Valve Control “Close” outputs turn on; Limit outputs turn off
(goes into Exceed condition); Alarms operate as if the process variable is
over-range.

Resistance Temperature Detector (RTD)

RTD Ranges Available

Range Min
in

C

Range Max
in

C

Range Min
in

F

Range Max
in

F

Resolution

-128.8

537.7

-199.9

999.9

0.1°

-199

800

-328

1472

1° (default)

Note:

Scale Range Upper Limit and Scale Range Lower Limit Configuration Mode parameters
can be used to restrict range.

This manual is related to the following products: