Operating menu and parameter description

79

Options:

• Command 1

Read out the primary variable

• Command 2

Read out the current and the main measured value as a percentage

• Command 3

Read out the dynamic HART variables and the current

• Command 9

Read out the dynamic HART variables including the related status

• Command 33

Read out the dynamic HART variables including the related unit

Factory settings

Command 2

Additional information

Commands 1, 2, 3 and 9 are universal HART commands.
Command 33 is a "Common-Practice" HART command.
More details on this are provided in the HART specifications.

Burst variable slot n

n = Number of burst variable slots (0 to 3)

Navigation

Expert ® Communication ® HART configuration ® Burst variable slot n

Prerequisite

This parameter can only be selected if the Burst mode option is enabled.

Description

Use this function to assign a measured variable to slots 0 to 3.

This assignment is only relevant for the burst mode. The measured variables are assigned to
the 4 HART variables (PV, SV, TV, QV) in the HART output (® ä 82) menu.

Options:

• Sensor 1 (measured value)
• Sensor 2 (measured value)
• Device temperature
• Average of the two measured values: 0.5 x (SV1+SV2)
• Difference between sensor 1 and sensor 2: SV1-SV2
• Sensor 1 (backup sensor 2): If sensor 1 fails, the value of sensor 2 automatically becomes the

primary HART

®

value (PV): sensor 1 (OR sensor 2)

• Sensor switching: If the value exceeds the configured threshold value T for sensor 1, the

measured value of sensor 2 becomes the primary HART

®

value (PV). The system switches back

to sensor 1 when the measured value of sensor 1 is at least 2 K below T: sensor 1 (sensor 2, if
sensor 1 > T)

The threshold value can be set with the Sensor switch set point parameter. With
temperature-dependent switching, it is possible to combine 2 sensors that offer advantages in
different temperature ranges.

Average: 0.5 x (SV1+SV2) with backup (measured value of sensor 1 or sensor 2 in the event of a
sensor error in the other sensor)

Factory settings

• Burst variable slot 0: sensor 1
• Burst variable slot 1: device temperature
• Burst variable slot 2: sensor 1
• Burst variable slot 3: sensor 1