5 post-connection check, Post-connection check – Pyromation T82 User Manual

Page 16

background image

Wiring

T82

16

- .

1

2

3

4

A0019556

å

7

Shielding and grounding the signal cable at one end with HART

®

communication

1

Optional grounding of the field device, isolated from cable shielding

2

Grounding of the cable shield at one end

3

Supply unit

4

Grounding point for HART

®

communication cable shield

NOTICE

If the shielding of the cable is grounded at more than one point in systems without

potential matching, power supply frequency equalizing currents can occur that damage

the signal cable or have a serious effect on signal transmission.

In such cases the shielding of the signal cable is to be grounded on only one side, i.e. it must
not be connected to the ground terminal of the housing (terminal head, field housing). The
shield that is not connected should be insulated!

5.5

Post-connection check

Device condition and specifications

Notes

Is the device or cable undamaged (visual inspection)?

--

Electrical connection

Notes

Does the supply voltage match the specifications on the nameplate?

U = 11 to 42 V DC

Do the cables have adequate strain relief?

--

Are the power supply and signal cables correctly connected?

(® ä 13)

Are all the screw terminals well tightened and have the connections of the spring terminals been
checked?

--

Are all the cable entries installed, tightened and sealed?

--

Are all the housing covers installed and tightened?

--