T82

Operating menu and parameter description

69

Additional information

The simulation value is defined in the Value current output parameter.

Value current output

Navigation

Diagnostics ® Simulation ® Value current output
Expert ® Diagnostics ® Simulation ® Value current output

Additional information

The Simulation current output parameter must be set to On.

Description

Use this function to set a current value for the simulation. In this way, users can verify the correct
adjustment of the current output and the correct function of downstream switching units.

User input

3.59 to 23.0 mA

Factory settings

3.59 mA

13.3.6 "Device reset" submenu

Device reset

Navigation

Diagnostics ® Device reset ® Device reset
Expert ® Diagnostics ® Device reset ® Device reset

Description

Use this function to reset the device configuration - either entirely or in part - to a defined state.

Options:

Not active
No action is executed and the user exits the parameter.

To factory defaults
All the parameters are reset to the factory setting.

To delivery settings
All the parameters are reset to the order configuration.The order configuration can differ from
the factory setting if customer-specific parameter values were defined when the device was
ordered.

Restart device
The device is restarted but the device configuration remains unchanged.

Factory settings

Not active