beautypg.com

T82 diagnostics and troubleshooting 31 – Pyromation T82 User Manual

Page 31

background image

T82

Diagnostics and troubleshooting

31

Diagno

stics

number

Event text

Remedial measures

Status

signal

from the

factory

Event

level from

the

factory

Changeab

le in

102

Sensor value too
high

1. Check process temperature.
2. Check sensor.
3. Check sensor type.

F

Alarm

104

Backup active

1. Check electrical connection sensor 1.
2. Replace sensor 1.
3. Check connection type.

M

Warning

105

Calibration interval 1. Execute calibration and reset calibration interval.

2. Switch off calibration counter.

M

Warning

1)

F

106

Backup not
available

1. Check electrical connection sensor 2.
2. Replace sensor 2.
3. Check connection type.

M

Warning

Diagnostics for the electronics

201

Electronic error

Replace electronics.

F

Alarm

221

Electronic
reference

Replace electronics.

F

Alarm

241

Electronic software 1. Device restart.

2. Device reset.
3. Replace electronics.

F

Alarm

261

Electronic modules Replace electronics.

F

Alarm

262

Module connection 1. Check whether the retainers and the connection of the

display module are correctly seated on the head transmitter.
2. Test the display module with other suitable head
transmitters.
3. Display module defective? Replace module.

M

Warning

283

Memory content

Replace electronics.

F

Alarm

301

Supply voltage

1. Increase supply voltage.
2. Check electrical connection for corrosion.

F

Alarm

Diagnostics for the configuration

401

Factory reset

Please wait during the reset process.

C

Warning

402

Configuration
initialization

Please wait during the initialization process

C

Warning

411

Up-/Download

Please wait during the Up-/Download process.

C

Warning

431

Factory calibration

Replace electronics.

F

Alarm

435

Linearization

1. Check configuration of sensor parameters.
2. Check configuration of special sensor linearization.
3. Contact service organisation.
4. Replace electronics.

F

Alarm

437

Configuration

1. Check configuration of sensor parameters.
2. Check configuration of special sensor linearization.
3. Check transmitter settings.
4. Contact service organisation.

F

Alarm

451

Data handling

Please wait during the data handling process.

C

Warning

483

Simulation input

Deactivate simulation.

C

Warning

485

Simulation
measured value

491

Simulation current
output