Д 78), Ä 78) – Pyromation T82 User Manual
Page 78

Operating menu and parameter description
T82
78
User input
• For a system in accordance with HART 5.0:
0 to 15
• For a system in accordance with HART 6.0:
0 to 63
Factory settings
0
Additional information
The measured value can only be transmitted via the current value is the address is set to "0". The
current is fixed at 4.0 mA for all other addresses (Multidrop mode).
No. of preambles
Navigation
Expert ® Communication ® HART configuration ® No. of preambles
Description
Use this function to define the number of preambles in the HART telegram.
User input
2 ... 20
Factory settings
5
Burst mode
Navigation
Expert ® Communication ® HART configuration ® Burst mode
Description
Use this function to switch the HART burst mode on or off.
Options:
•
Off
The device only sends data to the bus at the request of a HART master.
•
On
The device regularly sends data to the bus without being requested to do so.
Factory settings
Off
Burst command
Navigation
Expert ® Communication ® HART configuration ® Burst command
Prerequisite
This parameter can only be selected if the Burst mode option is enabled.
Description
Use this function to select the command whose response is sent to the HART master in the burst
mode.