Pyromation Series 810 1_8 DIN User Manual
Pyromation Equipment
1
/
16
-
1
/
8
DIN INDICATOR
CONCISE PRODUCT MANUAL (59344-3)
CAUTION:
Installation should be only performed by
technically competent personnel. Local Regulations
regarding electrical installation & safety must be observed.
1. INSTALLATION
The two indicators covered by this manual have different DIN case sizes (refer to
section 9). Some installation details vary between these models. These differences
have been clearly shown.
Note: The functions described in sections 2 to 8 are common to both models.
Installing Option Modules
1
/
16
Din Size Instruments
CPU PCB
Option Module 1
Option Module 2
Mounting Struts
Option Module A
Option Module 3
PSU PCB
1
/
8
Din Size Instruments
CPU PCB
Option Module B
(not used on
Indicator models)
Option Module 2
Option Module 1
Mounting Struts
Option Module A
Option Module 3
PSU PCB
To access modules 1 or A, first detach the PSU and CPU boards from the front by
lifting first the upper, and then lower mounting struts. Gently separate the boards.
a.
Plug the required option modules into the correct connectors, as shown below.
b.
Locate the module tongues in the corresponding slot on the opposite board.
c.
Hold the main boards together while relocating back on the mounting struts.
d.
Replace the instrument by aligning the CPU and PSU boards with their guides
in the housing, then slowly push the instrument back into position.
Note: Option modules are automatically detected at power up.
Option Module Connectors
1
/
16
Din Size Instruments
Option Slot 1
Connectors
PL7 & PL8
Option Slot 2
Connector
PL4A
Option Slot A
Connectors
PL5 & PL6
Option Slot 3
Connector
PL4B
1
/
8
Din Size Instruments
Option Slot B
(not used on
Indicator
models)
Option Slot 2
Connector
PL4A
Option Slot 1
Connectors
PL7 & PL8
Option Slot A
Connectors
PL5 & PL6
Option Slot 3
Connector
PL4B
Panel-Mounting
The mounting panel must be rigid, and may be up to
6.0mm (0.25inch) thick. Cut-out sizes are:
Cut-Out Dim A
Cut-Out Dim B
1
/
16
Din = 45mm
1
/
16
&
1
/
8
Din = 45mm
1
/
8
Din = 92mm
For n multiple instruments mounted side-by-side, cut-out
A is 48n-4mm (
1
/
16
Din) or 96n-4mm (
1
/
8
Din)
Tolerance +0.5, -0.0mm
Mounting Panel
Instrument
Housing
Ratchets
Gasket
Slide mounting clamp
over the instrument
housing towards rear face
of mounting panel until
the tongues engage in
ratchets and instrument is
clamped in position.
Hold instrument firmly in
position (apply pressure
to bezel only)
CAUTION:
Do not remove the panel gasket; it is a seal against dust and
moisture.
Rear Terminal Wiring
USE COPPER CONDUCTORS (EXCEPT FOR T/C INPUT)
Single Strand wire gauge: Max 1.2mm (18SWG)
1
/
16
Din Size Instruments
1
/
8
Din Size Instruments
These diagrams show all possible option combinations. The actual
connections required depend on the model and options fitted.
CAUTION:
Check information label on housing for correct operating
voltage before connecting supply to Power Input
Fuse: 100 – 240V ac – 1amp anti-surge
24/48V ac/dc – 315mA anti-surge
Note: At first power-up the message
is displayed, as described in
section 5 of this manual. Access to other menus is denied until configuration
mode is completed
2. SELECT MODE
Select mode is used to access the configuration and operation menu functions.
It can be accessed at any time by holding down and pressing .
The
legend is shown for 1 second, followed by the legend for the current mode
.
Press or to choose the required mode, then press to enter.
An unlock code is required to prevent unauthorised entry to Configuration, & Setup
modes. Press or to enter the unlock code, then press to proceed.
Mode
Legend
for 1 sec
followed
by
Set
Value
Description
Default
Unlock
Codes
Units
Display
(
1
/
8
Din
Only )
Operator
Normal operation
None
Set Up
Tailor settings for application
Configuration
Configure instrument for use
Product Info
Instrument information
None
Note: Automatic return to Operator Mode after 2 minutes without key activity.
3. CONFIGURATION MODE
First select Configuration mode from Select mode (refer to section 2).
Press to scroll through the parameters.
While this key is pressed, and up to 1
second after, the parameter legend is shown, followed by the current value
.
Press or to set the required value. Press to display
????
, press
accept the change, otherwise parameter will revert to previous value. To exit from
Configuration mode, hold down and press , to return to Select mode.
Note: Parameters displayed depends on how instrument has been configured.
Refer to user guide (available from your supplier) for further details.
Parameters marked * are repeated in Setup Mode.
Parameter
Legend
for 1 sec
followed
by
Set
Value
Adjustment Range &
Description
Default
Value
Units
Display
(
1
/
8
Din
Only )
Input
Range/Type
See following table for possible codes
Code Input Type &
Range
Code Input Type &
Range
Code Input Type &
Range
bC
bC
bC
bC
B: 100 - 1824 ºC
LLLL
.
C
C
C
C
L: 0.0 - 537.7 ºC
bF
bF
bF
bF
B: 211 - 3315 ºF
LLLL
.
F
F
F
F
L: 32.0 - 999.9 ºF
P24F
P24F
P24F
P24F
PtRh20% vs 40%:
32 - 3362 ºF
CC
CC
CC
CC
C: 0 - 2320 ºC
NC
NC
NC
NC
N: 0 - 1399 ºC
PTC
PTC
PTC
PTC
Pt100: –199 - 800 ºC
CF
CF
CF
CF
C: 32 - 4208 ºF
NF
NF
NF
NF
N: 32 - 2551 ºF
PtF
PtF
PtF
PtF
Pt100: –328 - 1472 ºF
JC
JC
JC
JC
J: –200 - 1200 ºC
rC
rC
rC
rC
R: 0 - 1759 ºC
Pt
Pt
Pt
Pt
.
C
C
C
C
Pt100: –128.8 - 537.7 ºC
JF
JF
JF
JF
J: –328 - 2192 ºF
rF
rF
rF
rF
R: 32 - 3198 ºF
Pt
Pt
Pt
Pt
.
F
F
F
F
Pt100: –199.9 - 999.9 ºF
j
j
j
j
.
C
C
C
C
J: –128.8 - 537.7 ºC
SC
SC
SC
SC
S: 0 - 1762 ºC
0 - 20 mA DC
j
j
j
j
.
F
F
F
F
J: –199.9 - 999.9 ºF
SF
SF
SF
SF
S: 32 - 3204 ºF
4 - 20 mA DC
KC
KC
KC
KC
K: –240 - 1373 ºC
tC
tC
tC
tC
T: –240 - 400 ºC
0 - 50 mV DC
KF
KF
KF
KF
K: –400 - 2503 ºF
tF
tF
tF
tF
T: –400 - 752 ºF
.
10 - 50 mV DC
k
k
k
k
.
C
C
C
C
K: –128.8 - 537.7 ºC
t
tt
t
.
C
C
C
C
T: –128.8 - 400.0 ºC
0 - 5 V DC
K
K
K
K
.
F
F
F
F
K: –199.9 - 999.9 ºF
t
tt
t
.
F
F
F
F
T: –199.9 - 752.0 ºF
1 - 5 V DC
LC
LC
LC
LC
L: 0 - 762 ºC
0 - 10 V DC
LF
LF
LF
LF
L: 32 - 1403 ºF
P24C
P24C
P24C
P24C
PtRh20% vs. 40%:
0 - 1850 ºC
2 - 10 V DC
Note: Decimal point shown in table indicates temperature resolution of 0.1°
Parameter
Legend
for 1 sec
followed
by
Set
Value
Adjustment Range &
Description
Default
Value
Units
Display
(
1
/
8
Din
Only )
Scale Range
Upper Limit
Scale Range Lower Limit +100
to Range Maximum
Max (Lin
= 1000)
Scale Range
Lower Limit
Range Minimum to
Scale Range Upper Limit -100
Min (Lin
= 0)
Decimal point
position
=XXXX, =XXX.X,
=XX.XX, =X.XXX
(non-temperature
ranges only)
°
Linear Range
Engineering
Units Display
None (Blank), °C or °F
1
/
8
Din units only where linear
inputs represent temperature
°
Multi-Point
Scaling
Mm
Mm
Mm
Mm
Enables or disables the input
multi-point scaling feature
Process High Alarm
Process Low Alarm
Alarm 1Type
No alarm
High Alarm 1*
Max
Low Alarm 1*
Alarm 1 value, adjustable within scaled
range, in display units
Min
(
Alm1
only = )
Alarm 1
Hysteresis*
1 LSD to full span in display units on
safe side of alarm
Alarm 2Type
High Alarm 2*
Max
Low Alarm 2*
Min
Al 2 Hysteresis*
Options as for alarm 1
!!!!
Alarm 3Type
High Alarm 3*
Max
Low Alarm 3*
Min
Al 3 Hysteresis*
Options as for alarm 1
*
*
*
*
Alarm 4Type
Options as for alarm 1
Parameter
Legend
for 1 sec
followed
by
Set
Value
Adjustment Range &
Description
Default
Value
Units
Display
(
1
/
8
Din
Only )
High Alarm 4*
Max
Low Alarm 4*
Min
Al 4 Hysteresis*
Options as for alarm 1
Alarm 5 Type
High Alarm 5*
Max
Low Alarm 5*
Min
Al 5 Hysteresis*
Options as for alarm 1
"
"
"
"
Alarm 1, direct, non-latching
Alarm 1, reverse, non-latching
"
"
"
"
Alarm 1, direct, latching
Alarm 1, reverse, latching
Alarm 2, direct, non-latching
Alarm 2, reverse, non-latching
Alarm 2, direct, latching
Alarm 2, reverse, latching
Alarm 3, direct, non-latching
Alarm 3, reverse, non-latching
Alarm 3, direct, latching
Alarm 3, reverse, latching
Alarm 4, direct, non-latching
Alarm 4, reverse, non-latching
Alarm 4, direct, latching
Alarm 4, reverse, latching
Alarm 5, direct, non-latching
Alarm 5, reverse, non-latching
Alarm 5, direct, latching
Alarm 5, reverse, latching
Logical Alarm 1 OR 2, direct
Logical Alarm 1 OR 2, reverse
Logical Alarm 1 OR 3, direct
Logical Alarm 1 OR 3, reverse
Logical Alarm 2 OR 3, direct
Logical Alarm 2 OR 3, reverse
Any active alarm, direct
Any active alarm, reverse
Retransmit PV Output
Output 1 Usage
####
0 to 10VDC (adjustable)
transmitter power supply*
for
linear
outputs,
"
"
"
"
for others
0 to 5 V DC output
0 to 10 V DC output
2 to 10 V DC output
0 to 20 mA DC output
Output 1 PV
Retransmit Type
4 to 20 mA DC output
Retransmit OP 1
Scale maximum
Display value between, -1999 & 9999
at which Output 1 will be at maximum
Range
max
Retransmit OP 1
Scale minimum
Display value between, -1999 & 9999
at which Output 1 will be at minimum
Range
min
TxPSU 1 level
Output 1 Power Supply (0 to 10VDC)*
.
Output 2 Usage
As for Output 1 Usage
Output 2 PV
Retransmit Type
As for Output 1 PV Retransmit Type
Retransmit OP2
Scale Maximum
As for Retransmit Output 1 Scale Maximum
Retransmit OP2
Scale Minimum
As for Retransmit Output 1 Scale Minimum
TxPSU 2 level
Output 2 Power Supply (0 to 10VDC)*
.
Output 3 Usage
As for Output 1 Usage
Output 3 PV
Retransmit Type
As for Output 1 PV Retransmit Type
Retransmit OP3
Scale maximum
As for Retransmit Output 1 Scale Maximum
Retransmit OP3
Scale minimum
As for Retransmit Output 1 Scale Minimum
TxPSU 3 level
Output 3 Power Supply (0 to 10VDC)*
.
Output 4 Usage
Output 5 Usage
Alarm output options as for
Output 1 Usage
Display Strategy
$
$
$
$
, , , , or
%%%%
(refer to section 6)
Permanent Red
Permanent Green
&
&
&
&
Red to Green on any alarm
Display Colour
&
&
&
&
Green to Red on any alarm
&
&
&
&
####
'
'
'
'
ASCII
Mm
Mm
Mm
Mm
Modbus with no parity
Mm
Mm
Mm
Mm
Modbus with Even Parity
Serial
Communication
Protocol
Mm
Mm
Mm
Mm
Modbus with Odd Parity
Mm
Mm
Mm
Mm
Comms Bit Rate
. , . , .
(
((
(
,
)
))
)
.
%%%%
or
)
))
)
.
kbps
.
(
((
(
Comms Address
to
(Modbus), to
))
))
))
))
(ASCII)
Continued on next page…
A