T82
Operating menu and parameter description
75
Call./v. Dusen coeff. A, B and C
Navigation
Expert ® Sensor ® Sensor n ® Linearization ® Call./v. Dusen coeff. A, B, C
Prerequisite
The RTD platinum (Callendar/Van Dusen) option is enabled in the Sensor type parameter.
Description
Use this function to set the coefficients for sensor linearization based on the Callendar/Van Dusen
method.
Factory settings
• A: 3.910000e-003
• B: -5.780000e-007
• C: -4.180000e-012
Polynomial coeff. R0
Navigation
Expert ® Sensor ® Sensor n ® Linearization ® Polynomial coeff. R0
Prerequisite
The RTD poly nickel or RTD polynomial copper option is enabled in the Sensor type parameter.
Description
Use this function to set the R0 value for linearization of nickel/copper sensors.
User input
40.000 to 1
050.000 Ohm
Factory settings
100.00 Ohm
Polynomial coeff. A, B
Navigation
Expert ® Sensor ® Sensor n ® Linearization ® Polynomial coeff. A, B
Prerequisite
The RTD poly nickel or RTD copper polynomial option is enabled in the Sensor type parameter.
Description
Use this function to set the coefficients for sensor linearization of copper/nickel resistance
thermometers.
Factory settings
Polynom coeff. A = 5.49630e-003
Polynom coeff. B = 6.75560e-006
"Diagnostic settings" submenu
Calibration counter start
Navigation
Expert ® Sensor ® Diagnostic settings ® Calibration counter start