T82
Operating menu and parameter description
61
Failure current
Navigation
Setup ® Advanced setup ® Current output® Failure current
Expert ® Output ® Failure current
Prerequisite
The Max. option is enabled in the Failure mode parameter.
Description
Use this function to set the value the current output adopts in an alarm condition.
User input
21.5 to 23.0 mA
Factory settings
22.5
Current trimming 4 mA
Navigation
Setup ® Advanced setup ® Current output® Current trimming 4 mA
Expert ® Output ® Current trimming 4 mA
Description
Use this function to set the correction value for the current output at the start of the measuring
range at 4 mA (® ä 59).
User input
3.85 to 4.15 mA
Factory settings
4 mA
Current trimming 20 mA
Navigation
Setup ® Advanced setup ® Current output® Current trimming 20 mA
Expert ® Output ® Current trimming 20 mA
Description
Use this function to set the correction value for the current output at the end of the measuring
range at 20 mA (® ä 59).
User input
19.850 to 20.15 mA
Factory settings
20.000 mA