Operating menu and parameter description

T82

56

Device temperature alarm

Navigation

Setup ® Advanced setup ® Device temperature alarm

Description

Use this function to select the category (status signal) as to how the device reacts when the
electronics temperature of the transmitter exceeds or falls below the limit value < -40 °C (-40 °F)
or > +85 °C (+185 °F).

Options:

• Off
• Out of specification (S)
• Failure (F)

Factory settings

Out of specification (S)

Device tag

Navigation

Setup ® Advanced setup ® Device tag
Diagnostics ® Device information ® Device tag
Expert ® Diagnostics ® Device information ® Device tag

Description

Use this function to enter a unique name for the measuring point so it can be identified quickly
within the plant. The name is displayed in the header of the plug-in display. (® е 9, д 20)

User input

Max. 32 characters, such as letters, numbers or special characters (e.g. @, %, /)

Factory settings

-none-

Locking status

Navigation

Setup ® Advanced setup ® Locking status
Expert ® Locking status

Description

Use this function to view the device locking status. The DIP switch for hardware locking is fitted
on the display module. When write protection is activated, write access to the parameters is
disabled. (® д 20)