Part D Technical Data, Measuring Principle and Block Diagram Sect. 10.1

05/2002

IFC 210 E

79

10

7HFKQLFDOGDWD

10.1 IFC 210 E signal converter

5DQJHRIDSSOLFDWLRQ

Flow measurement of liquid products

0RGHRIRSHUDWLRQDQGV\VWHPVWUXFWXUH

Measurement principle

Faraday`s laws of induction

Modularity

Measuring system consisting of

signal converter and separate primary head

Versions – signal converter

IFC 210 E (Standard)

- Standard version with large graphic LC display and

integrated HART

®

interface

IFC 210 E / RS 485 (Option)

- same as standard version, but additionally with
RS 485 interface

IFC 210 E / _ / EEx (Option)

- same as standard version, for operation with
primary heads installed in hazardous areas

Interface module (Option)

- RS 485 / Profibus PA (in preparation)

Versions – primary head

Refer to Technical Data in separate Installation
Instructions

,QSXW

Measured variable

Volumetric flow rate

(electrode voltage from primary head)

Measuring range

Dependent on meter size of primary head

see also Table in Sect. 10.2

Full-scale range

6 Liter/h to 86 860 m

3

/h, corresponding

flow velocity v = 0.3 to 12 m/s

Selectable units

m

3

/h, Liter/s, US Gallons/min or freely selectable

unit, e.g. Liter/day

2XWSXW

Output/input signal

Current-

Pulse-

Status-

Control-

Output output output input

Operation active/

passive

active/

passive

passive Passive

Failure signal (error)

22 mA,

and others

– yes –

Load impedance

max. 800

– – –

Low

flow

Yes – yes –

F/R mode

Yes

yes

Other functions
detailed technical data (see below)

Yes

yes

yes

yes