KROHNE IFC 210 E-EEx EN User Manual
Page 35
Part B IFC 210 Signal converter Sect. 4.4
05/2002
IFC 210 E
35
Fct.
Display-Texts
Description and settings
3.06 Application
Set
application
conditions
Flow
Set characterization for flow
• Steady
(steady flow, max. 150% of Q
100%
)
• Pulsating
(pulsating flow, up to 1000% of Q
100%
e.g. caused by reciprocating pumps, refer to Sect. 6.4)
Press
↵
key to transfer to subfunction “Empty Pipe”.
Empty Pipe
Signal when measuring tube is empty (refer to Sect. 6.3 )
• no • yes (possible only with built-in option)
Press
↵
key to return to Fct. 3.06 “Application”.
3.07
Hardware
Assign outputs and inputs to terminals B1 and B2
Terminal B1
Define function of terminal B1 (valid for Fct. 1.07)
• Statusoutput • Controlinput (
Select with
↑
key.
)
Press
↵
key to transfer to subfunction “Terminal B2”.
Terminal B2
Define function of terminal B2 (valid for Fct. 1.08)
• Statusoutput • Controlinput (
Select with
↑
key.
)
Press
↵
key to transfer to subfunction “Fieldcurrent”.
Fieldcurrent
Define field current supply
• Intern
• Extern (> DN 1600 / > 64“ with power driver)
Press
↵
key to return to Fct. 3.07 “Hardware”.
3.08
Location
Set measuring point tag
Factory
setting: ALTOMETER
Characters assignable to each place:
• A-Z, a-z, 0-9 or „-“ (=blank character).)
Press
↵
key to return to Fct. 3.08 “Location”.
3.09
Communication
Set comminucation interface
• Off
(switched off))
•
HART (HART
®
-interface switched on))
• KROHNE
(KROHNE RS 485-interface switched on),
(only provided if daughter board installed (option).)
• Address:
„HART“ 00-15 / „KROHNE“ 000-239
• Baud rate: 1200, 2400, 4800, 9600 or 19200
(appears with selection “KROHNE” only)“)
Press
↵
key to return to Fct. 3.09 “Communication”.