Sect. 5.8

Part B IFC 210 Signal converter

IFC 210 E

05/2002

44

5.8

Statusoutput B1 and / or B2

Statusoutput: Fct. 1.07 (output terminal B1) and Fct. 1.08 (output terminal B2)
Press

key.

Select function of status outputs,

Select with

or

key.

Off

switched off, no function

On

indicates that flowmeter is operative

All Error

indicates all errors

Only Fatal

indicates fatal errors only

Signum
I
or P

for V/R mode, measurement in both flow directions,
see also Sect. 5.10

Overrange I or P

signals overranging of outputs

Low Flow Cutoff
I
or P

signals active low-flow cutoff (SMU)

I = I only
P = All

Invers B1

Status output B2 inverse function to B1
(only provided if B1 and B2 are set as status output)

Trip Point

see also Sect. 5.12

Define flow direction (characteristics) for limit value

+ direction

- direction

Select with

or

key

2 directions

Define limit value

NO contact: XXX > YYY

XXX -

YYY

NC contact: XXX < YYY

0...150%

-

0...150%

Hysteresis: Difference

XXX

to YYY

Transfer to number setting with

key,

1st number (cursor)with negative image.

Change negative-image number (cursor) with

or

key, move

cursor 1 place to right or left with

and

key, resp..

Auto Range

see also Sect. 5.11

Setting range:

05 – 80 %

ratio of upper to lower range, 1:20 to 1:1.25

(value must be greater than that of Fct. 1.03 L.F.Cutoff , s. also Sect. 5.3)

Empty Pipe

Signals that tube is empty (only with built-in option), see Sect. 6.4 – 6.6.

Press

key to return to Fct. 1.07 or 1.08 Statusoutput.

Characteristics of status outputs

Switch open

Switch closed

Off (switched off)

no function

On (e.g. operation indicator)

power OFF

power ON

Empty Pipe

Tube is empty

Tube is full

Signum I or P

Forward flow

Reverse flow

Overflow I or P

not overranged

overranged

Low Flow Cutoff I or P inactive

active

Invers B1

B2 closed

B2 open

Trip Point (limit switch)

inactive

active

Auto Range

high range

low range

All Error (all errors)

errors

no error

Only Fatal (fatal errors only)

errors

no error

Please refer to Sect. 3.2 Factory settings .

Refer to Sect. 2.5 for connection diagrams, and to Sect. 5.22 for characteristics.