Description of hart interface, 3 outputs and hart, Dynamic variable and device variable – KROHNE IFC 100 Converter EN User Manual
Page 94
9
DESCRIPTION OF HART INTERFACE
94
IFC 100
www.krohne.com
07/2010 - 4000041004 - MA IFC 100 R04 en
9.3 Outputs and HART
®
Dynamic variable and device variable
The signal converter is available with various output combinations.
The connection of the terminals A…D to the HART
®
dynamic variables PV, SV, TV and 4V depends
on the device version.
PV = Primary Variable; SV = Secondary Variable; TV = Third Variable; 4V = Fourth Variable
The signal converter can provide up to 8 measured values. The measured values are accessible
as so-called HART
®
device variables and can be connected to the HART
®
dynamic variables. The
availability of these variables depends on the device versions and the settings.
Code = device variable code
Device variables
Signal converter version
HART
®
dynamic variable
PV
SV
TV
4V
Basis I/O, terminals
A
D
-
-
HART
®
device variable
Code
Type
Explanations
flow speed
20
linear
-
volume flow
21
linear
mass flow
22
linear
conductivity
24
linear
coil temperature
23
linear
counter 1 (C)
6
totalizer
-
counter 2 (D)
14
totalizer
diagnosis value
25
linear
Function and availability depends on
diagnosis value setting.
.book Page 94 Friday, July 9, 2010 12:29 PM