Operation – KROHNE IFC 100 Converter EN User Manual
Page 64
6
OPERATION
64
IFC 100
www.krohne.com
07/2010 - 4000041004 - MA IFC 100 R04 en
No.
Function
Settings / descriptions
C4 I/O HART
C4
I/O HART
Selection / display of the 4 dynamic variables (DV) for HART
®
.
The HART
®
current output (terminal A basic I/Os) always has a fixed link to
the primary variables (PV). Fixed links of the other DVs (1-3) are only
possible if one additional analogue output (frequency) is available; if not, the
measurement can be freely selected from the following list: see Fct. A4.1
"measurement".
stands for 1, 3 or 4
X stands for connection terminals A, C or D
C4.1
PV is
Current output (primary variable)
C4.2
SV is
(secondary variable)
C4.3
TV is
(tertiary variable)
C4.4
4V is
(4th variable)
C4.5
HART units
Changes units of DVs (dynamic variables) in the display
Break: return with ^ key
HART display
®
: copies the settings for the display units to the settings for
DVs
Standard: sets factory defaults for DVs
C4. .1
current out X
Shows the current analogue measured value of the linked current output.
The measurement cannot be changed!
C4. .1
frequency out X
Shows the current analogue measured value of the linked frequency output,
if present. The measurement cannot be changed!
C4. .1
HART dynamic var.
Measurements of the dynamic variables for HART
®
.
Linear measurements: volume flow / mass flow / diagnosis value / flow
speed / coil temperature / conductivity
Digital measurements: counter 1 / counter 2 / operating hours
No.
Function
Settings / descriptions
C5 device
C5.1 device info
C5.1
device info
Grouping of all functions that have no direct effect on the measurement or
any output.
C5.1.1
Tag
Settable characters (max. 8 digits):
A…Z; a…z; 0…9; / - , .
C5.1.2
C number
CG number, non-alterable (input/output versions)
C5.1.3
device serial no.
Serial no. of the system.
C5.1.4
electronic serial no.
Serial no. of the electronic assembly, cannot be changed.
C5.1.5
SW.REV.MS
Serial no. of the circuit board, version no. of the main software, production
date of the circuit board
C5.1.6
Electronic Revision ER
Reference identification number, electronic revision and production date of
the device; includes all hardware and software changes
.book Page 64 Friday, July 9, 2010 12:29 PM