6.5 Status messages and diagnostic information

Operational faults in device

Messages on the display Description

Actions

Status: F _ _ _ _ _

Operational fault in device, mA output ≤
3.6 mA or set fault current (depending
on the seriousness of the fault), status
output open, pulse / frequency output:
no pulses

Repair necessary.

F error in device

Fault or failure of device. Parameter or

hardware error. No measurement possible.

Group message, when one of the following

or some other severe error occurs.

F IO 1

Error, operational fault in IO 1. Parameter

or hardware error. No measurement

possible.

Load settings (Fct. C4.6.3) (backup 1,

backup 2 or factory settings). If status

message still does not disappear, replace

electronic unit.

F parameter

Error, operational fault of data manager,

electronic unit, parameter or hardware

error. Parameters no longer usable.

F IO 2

Error, operational fault in IO 2. Parameter

or hardware error. No measurement

possible.

F configuration

Invalid configuration: display software, bus

parameter or main software do not match

existing configuration.

If device configuration unchanged:

defective, replace electronic unit.

F display

Error, operational fault in display.

Parameter or hardware error. No

measurement possible.

Defective, replace electronic unit.

F sensor electronic

Error, operational fault in sensor

electronics. Parameter or hardware error.

No measurement possible.

Defective, replace electronic unit.

F sensor global

Data error in the global data of the

measuring sensor electronic equipment.

Load settings (Fct. C5.6.3) (backup 1,

backup 2 or factory settings). If status

message still does not disappear, replace

electronic unit.

F sensor local

Data error in the local data of the measuring

sensor electronic equipment.

Defective, replace electronic unit.

F field current local

Data error in the local data of the field

current supply.

Defective, replace electronic unit.

F current output A

Error, operational fault in current output.

Parameter or hardware error. No

measurement possible.

Defective, replace electronic unit.

F software user interface

Fault revealed by CRC check of operation

software.

Replace electronic unit.

F hardware settings

The set hardware parameters do not match

the identified hardware. A dialogue appears

in the display.

Answer queries in dialogue mode, follow

directions.

Defective, replace electronic unit.

F hardware detection

Existing hardware cannot be identified.

Defective, replace electronic unit.

F RAM/ROM error IO1

A RAM or ROM error is detected during the

CRC check.

Defective, replace electronic unit.

F RAM/ROM error IO2

F Fieldbus

Malfunction of the Fieldbus interface.

-