beautypg.com

Electrical connections – KROHNE IFC 100 Converter EN User Manual

Page 25

background image

ELECTRICAL CONNECTIONS

4

25

IFC 100

www.krohne.com

07/2010 - 4000041004 - MA IFC 100 R04 en

4.4.5 Preparing signal cable A, connection to measuring sensor

• The outer shield (60) is connected in the terminal compartment of the measuring sensor

directly via the shield and a clip.

• Bending radius: ≥ 50 mm / 2"

Required materials

• PVC insulating tube, Ø2.0...2.5 mm / 0.08...0.1"
• Heat-shrinkable tubing
• Wire end ferrule to DIN 46 228: E 1.5-8 for the stranded drain wire (1)
• 2x wire end ferrules to DIN 46 228: E 0.5-8 for the insulated conductors (2, 3)

1 Strip the conductor to dimension a.
2 Trim the outer shield (60) to dimension b and pull it over the outer sheath.
3 Remove the stranded drain wire (6) of the outer shield and the inner shield (10). Make sure not

to damage the stranded drain wire (1) of the inner shield.

4 Slide an insulating tube over the stranded drain wire (1).
5 Crimp the wire end ferrules onto conductors 2 and 3 and the stranded drain wire (1).
6 Pull the heat-shrinkable tubing over the prepared signal cable.

INFORMATION!
Assembly materials and tools are not part of the delivery. Use the assembly materials and tools
in compliance with the applicable occupational health and safety directives.

Figure 4-5: Preparing signal cable A, connection to measuring sensor

a = 50 mm / 2"
b = 10 mm / 0.39"

.book Page 25 Friday, July 9, 2010 12:29 PM