beautypg.com

Description of hart interface – KROHNE IFC 100 Converter EN User Manual

Page 92

background image

9

DESCRIPTION OF HART INTERFACE

92

IFC 100

www.krohne.com

07/2010 - 4000041004 - MA IFC 100 R04 en

9.2.2 Multi-Drop connection (2-wire connection)

In the case of a Multi-Drop connection, up to 15 devices may be installed in parallel (this signal
converter and other HART

®

devices).

The current outputs of the devices must be passive!

1 Primary Master
2 HART

®

modem

3 HART

®

signal

4 Other HART

®

devices or this signal converter (see also 7)

5 Signal converter terminals A (C)
6 Signal converter terminals A- (C-)
7 Signal converter with address > 0 and passive current output, connection of max. 15 devices (slaves) with 4…20 mA
8 Secondary Master
9 Power supply
10 Load ≥ 250 Ω (Ohm)

.book Page 92 Friday, July 9, 2010 12:29 PM