beautypg.com

Electrical connections – KROHNE IFC 100 Converter EN User Manual

Page 42

background image

4

ELECTRICAL CONNECTIONS

42

IFC 100

www.krohne.com

07/2010 - 4000041004 - MA IFC 100 R04 en

Pulse/frequency output passive

• U

ext

≤ 32 VDC

• f

max

in operating menu set to 100 Hz < f

max

≤ 10 kHz:

I ≤ 100 mA at ≤ 10 kHz (overcontrol up to f

max

≤ 12 kHz)

open:
I ≤ 0.1 mA at U

ext

= 5 V

I ≤ 0.5 mA at U

ext

= 24 V

I ≤ 0.7 mA at U

ext

= 32 V

closed:
U

0, max

= 0.8 V at I ≤ 1 mA

U

0, max

= 1.5 V at I ≤ 10 mA

U

0, max

= 3.5 V at I ≤ 100 mA

• If the following maximum load resistance R

L, max

is exceeded, the load resistance R

L

must be

reduced accordingly by parallel connection of R:
f ≤ 1 kHz: R

L, max

= 10 kΩ

f ≤ 10 kHz: R

L, max

= 2 kΩ

• The minimum load resistance R

L, min

is calculated as follows:

R

L, min

= (U

ext

- U

0

) / I

max

• Can also be set as status output; for the electrical connection refer to status output

connection diagram.

• The output is closed when the device is de-energized.

INFORMATION!

For frequencies above 100 Hz, shielded cables are to be used in order to reduce effects from
electrical interferences (EMC).

Shielding takes place at the electrical connection (S) of the output terminal block.

CAUTION!
Observe connection polarity.

Figure 4-18: Pulse/frequency output passive P

p

.book Page 42 Friday, July 9, 2010 12:29 PM