Voltage and current parameter definitions -6, E 3-2 d – KEPCO BOP-GL 1KW Operator Manual Firmware Ver.3.05 and higher User Manual
Page 68
![background image](/manuals/367930/68/background.png)
3-6
BOP-1K-GL 022814
TABLE 3-2. VOLTAGE AND CURRENT PARAMETER DEFINITIONS
Term
Definition
To modify
refer to
PAR.
+E
Onom
–E
Onom
The nominal (rated) output voltage of the unit determined by model; e.g. for
a BOP 36-28GL, ±E
Onom
is 36V.
N/A
+I
Onom
–I
Onom
The nominal (rated) output current of the unit determined by model; e.g. for
a BOP 36-28GL, ±I
Onom
is 28A.
N/A
+Voltage
–Voltage
Voltage mode only.
Positive (+) and negative (–) output voltage values
established by remote command.
Range (+): 0 to +Voltage max
Range (–): 0 to –Voltage min
+Voltage max
–Voltage min
Voltage mode only.
Maximum (positive) and minimum (maximum
negative) voltage that can be set.
Value (+): 0 to +E
Onom
Value (–): 0 to –E
Onom
+Current Protect
–Current Protect
Voltage mode only.
Defines maximum (+) current and Minimum (maximum
negative) (–) that unit can source or sink.
Range (+): +Current Protect min to +Current Protect max
Range (–): –Current Protect max to –Current Protect min
+Current Protect Max
–Current Protect Min
Voltage mode only.
Maximum setting for +Current Protect and Minimum
(maximum negative) setting for –Current Protect.
Value (+): +Current Protect min to (1.01 x +Current max)
Value (–): –Current Protect max to (1.01 x –Current min)
Minimum (box)
+Current Protect Min
–Current Protect Max
Voltage mode only.
Minimum (positive) setting for +Current Protect and
maximum (maximum negative) setting for –Current Protect. Values of ±Cur-
rent Protect between +Current Protect Min and –Current Protect Max (near
zero) are not allowed.This zone (also referred to as the minimum (box) is
automatically calculated by the BOP (see Figure 1-3).
N/A
+Voltage Protect
–Voltage Protect
Current mode only.
Maximum positive (+) and minimum (maximum
negative) (–) voltage that can appear at the output.
Range (+): +Voltage Protect min to +Voltage Protect max
Range (–): –Voltage Protect max to –Voltage Protect min
+Voltage Protect Max
–Voltage Protect Min
Current mode only.
Maximum (positive) setting for +Voltage Protect and
Minimum (maximum negative) setting for –Voltage Protect.
Value (+): +Voltage Protect min to (1.01 x +Voltage max)
Value (–): –Voltage Protect max to (1.01 x –Voltage min)
Minimum (box)
+Voltage Protect Min
–Voltage Protect Max
Current mode only.
Minimum (positive) setting for +Voltage Protect and
maximum (maximum negative) setting for –Voltage Protect. Values of ±Volt-
age Protect between +Voltage Protect Min and –Voltage Protect Max (near
zero) are not allowed. This zone (also referred to as the minimum (box) is
automatically calculated by the BOP (see Figure 1-3).
N/A
+Current
–Current
Current mode only.
Positive and negative output current established by
remote command.
Range (+): 0 to +Current max
Range (–): 0 to –Current min
+Current max
–Current min
Current mode only.
Maximum (positive) and minimum (maximum
negative) current that can be set.
Value (+): 0 to +I
Onom
Value (–): 0 to –I
Onom