beautypg.com

3 voltage and current parameters, 1 hidden voltage and current protect limits, Caution – KEPCO BOP-GL 1KW Operator Manual Firmware Ver.3.05 and higher User Manual

Page 67: The unit, Voltage and current parameters -5, Hidden voltage and current protect limits -5

background image

BOP-1K-GL 022814

3-5

b. Set S2 to select standalone or multiple unit operation.

c. Set S1 with valid GPIB address from 0 to 30.

CAUTION: DO NOT repeatedly toggle the circuit breaker/switch as this may damage the

unit.

2. Set POWER ON/OFF circuit breaker/switch (1, Figure 3-1) on front panel to ON. If actuator

does not lock when released, wait a few seconds before trying again. The circuit breaker is
“trip-free” design; if overload exists, contacts cannot be held closed by actuator.

3. Unit performs self-test upon power-up initialization. If the unit passes self-test, the

POWER/FAULT/LIMIT light turns green and the unit is ready for operation; if it fails, the light
turns red.

3.3.3

VOLTAGE AND CURRENT PARAMETERS

Table 3-2 defines the voltage and current parameters used in this manual and provides refer-
ences to the SCPI commands and queries associated with the parameter.

3.3.4

VOLTAGE/CURRENT PROTECT LIMITS (LIMIT CHANNEL SOFTWARE LIMITS)

These values are the references for the complementary channels: voltage in current mode and
current in voltage mode. The range for these values is between a minimum (box) value (see Fig-
ure 1-3) and 1% above the rated nominal value (see PAR. 3.3.5). If the unit is in voltage mode, it
will enter current protect mode when the load demands more current and energy than permitted
by the ±current protect settings. Similarly, if the unit is in current mode, it will enter voltage pro-
tect mode if the load demands more voltage and energy than permitted by the ±voltage protect
settings. When the protect settings are exceeded, the protection channel limits the output cur-
rent or voltage, the POWER/FAULT/LIMIT LED lights orange (LIMIT), and the power supply
continues operation in the complementary mode of operation.

The BOP can be configured to program the protection limits as a single value that applies to
both protection channels using a common digital command, either CURR:PROT:LIM (see PAR.
B.37) or VOLT:PROT:LIM (see PAR. B.104) or by using or individual commands:
CURR:PROT:LIM:POS (see PAR. B.41), CURR:PROT:LIM:NEG (see PAR. B.39),
VOLT:PROT:LIM:POS (see PAR. B.108), VOLT:PROT:LIM:NEG (see PAR. B.106) to program
individual settings for positive and negative protection limits.

3.3.4.1

HIDDEN VOLTAGE AND CURRENT PROTECT LIMITS

The BOP employs two back-up channels which function as safety backups if a main channel
fails. The backup channel limits are fixed and not user accessible. These limits are set to 5%
over the nominal (rated) values for voltage or current. If the software limits for a main channel is
changed (PAR. 3.3.5), the corresponding protect channel limit is automatically changed to be
5% of the nominal (rated) value above the user-programmed software limit.