MS-9050 Series Manual — P/N 52413:G 4/14/2014
Programming
Master Programming Level
ANN-I/O Zone Option
If Zone is selected as the module option, the first ten LED driver outputs on the ANN-I/O module
will display the system status information. The remaining 20 LED driver outputs on the module
will display the active/alarm status of each zone. The LED assignments for the ANN-I/O module
will be as follows.
ANN-I/O Point Option
If Point is selected as the module option, the first ten LED driver outputs on the first ANN-I/O
module will display the system status information. The remaining 30 LED driver outputs on the
first module and 20 LED driver outputs on the second module will be used to display the
active/alarm status of each point in the Point Range programmed for that particular module. The
Module LED
Function
1
AC Fault
2
Fire Alarm
3
Supervisory
4
Trouble
5
Alarm Silenced
6
Not Used
7
Not Used
8
Not Used
9
Not Used
10
Not Used
11
Zone 00 - Active/Alarm
12
Zone 01 - Active/Alarm
13
Zone 02 - Active/Alarm
14
Zone 03 - Active/Alarm
15
Zone 04 - Active/Alarm
16
Zone 05 - Active/Alarm
17
Zone 06 - Active/Alarm
18
Zone 07 - Active/Alarm
19
Zone 08 - Active/Alarm
20
Zone 09 - Active/Alarm
21
Zone 10 - Active/Alarm
22
Zone 11 - Active/Alarm
23
Zone 12 - Active/Alarm
24
Zone 13 - Active/Alarm
25
Zone 14 - Active/Alarm
26
Zone 15 - Active/Alarm
27
Zone 16 - Active/Alarm
28
Zone 17 - Active/Alarm
29
Zone 18 - Active/Alarm
30
Zone 19 - Active/Alarm
31
Not Used
32
Not Used
33
Not Used
34
Not Used
35
Not Used
36
Not Used
37
Not Used
38
Not Used
39
Not Used
40