Conventional – Fire-Lite MS-9050UDC Addressable Fire Alarm Control Panel User Manual
Page 70
70
MS-9050 Series Manual — P/N 52413:G 4/14/2014
Programming
Master Programming Level
Pre-signal
To enable the Pre-signal feature, press 1 while viewing Edit Monitor Screen #3 until the display
reads Pre-signal Yes. Each press of the 1 key will cause the display to toggle between Pre-signal
Yes and Pre-signal No. Refer to“Presignal” on page 134 for additional information.
Walktest
The Walktest feature allows one person to test the system devices without the necessity of manually
resetting the control panel after each device activation. To enable devices, which are connected to
a monitor module, for the Walktest feature, press 1 while viewing the Edit Monitor Screen #4 until
the display reads Walktest Yes. Each press of the 1 key will cause the display to toggle between
Walktest Yes and Walktest No. Refer to“Walktest” on page 136 for additional information.
Zone Assignment
A maximum of five zones can be programmed to each addressable monitor module. Pressing 2
while viewing Edit Monitor Screen #4 displays the following screen:
Note that Z** represents the Zone Number(s) corresponding to this device. The factory default for
an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on the first 0
to the left. Enter the two digit number corresponding to the zone that is to be assigned to this
device. The cursor moves to the next Z** designation. Continue entering zone assignments or the
remaining zones can be left blank or programmed as general alarm zones Z00. When all desired
changes have been made, press the Enter key to store the zone assignments. The display will return
to the Edit Monitor Screen #4.
Drill-Switch
Acts like panel Drill Key
PAS-Bypass
PAS Disable
HVAC RESTART
Switch
Drill-Switch AR
Acts like panel Drill Key, nonlatching (tracking)
6
1 Conventional 2-wire smoke detectors may be powered using an external power supply
with an SLC Control Relay Module programmed for Resettable Power operation. A
Control Relay Module set to the Resettable Power type will follow the main circuit
board 24 VDC resettable power unless the control module is disabled.
2 Use only these Monitor Type IDs for the Zone Modules (MMF-302). The Zone
Modules will not function correctly if any other Type ID is used.
3 Combination systems employing these non-fire monitor types require the SLC loop to
be programmed by the installer for Style 4 operation and isolator modules must be
employed on each non-fire branch of the SLC as per Figure 13 in the Fire-Lite SLC
Wiring Manual (document number 51309). Fire and non-fire devices must not be used
on the same SLC branch.
4 For entries ending in AR, AR refers to AutoResettable.
5 For HVAC RESTART AND HVAC OVRRIDE descriptions, refer to“HVAC Control” on
6 Drill Switch Auto-Resettable turns on the NACs and any control module mapped to the
Drill Switch zone.
Table 3.1 Monitor Types
EDIT MONITOR
1=PRE-SIGNAL
Edit Monitor Screen #3
EDIT MONITOR
1=WALKTEST
2=ZONE ASSIGNMENT
00 QQ QQ QQ QQ
Edit Monitor Screen #4
MON ZONE ASSIGN
Z00 ZQQ ZQQ ZQQ ZQQ
Zone Assignment Screen