Zones installed, Zones enabled, Zones disabled – Fire-Lite MS-9050UDC Addressable Fire Alarm Control Panel User Manual
Page 79: Zone type
MS-9050 Series Manual — P/N 52413:G 4/14/2014
79
Master Programming Level
Programming
Pressing 2 will cause the display to change to Pre-signal 18 On. Each press of the 2 key will cause
the display to toggle between Pre-signal 18 On and Pre-signal 18 Off. When Zone 18 is pro-
grammed On, a Pre-signal activation of any device will cause Zone 18 to activate. By assigning
Zone 18 to a control module in the Programming Zone Assignment Screen, an output device con-
nected to the control module can be used to indicate a Pre-signal condition in the control panel. Do
not assign Zone 18 to a Notification Appliance Circuit when using this zone to indicate a Pre-signal
condition. Attempting to do so will generate an error message and will be prevented by software
checks.
Pressing 3 will cause the display to change to Two Stage 19 On. Each press of the 3 key will cause
the display to toggle between Two Stage 19 On and Two Stage 19 Off. Refer to “Two Stage Opera-
tion” on page 88 for a description of this feature.
Zones Installed
Pressing 1 for Zones Installed, while viewing Zone Setup Screen #2, will display a screen similar to
the following:
This display will show all of the zones that have been programmed into the control panel.
Zones Enabled
Pressing 2 for Zones Enabled, while viewing Zone Setup Screen #2, will display a screen similar to
the following:
This display will show all of the zones that are enabled in the control panel.
Zones Disabled
Pressing 3 for Zones Disabled, while viewing Zone Setup Screen #2, will display a screen similar
to the following:
This display will show all of the zones that are disabled in the control panel.
Zone Type
Zone Types must be programmed only if a DACT, programmed for zone reporting, is installed on
the control panel. Pressing 1 for Zone Types, while viewing Zone Setup Screen #3, will display a
screen similar to the following:
ZONE SETUP
1=ZONES INSTALLED
2=ZONES ENABLED
3=ZONES DISABLED
Zone Setup Screen #2
ZONES INSTALLED
00 01 02 03 04 05
Zones Installed Screen
ZONES ENABLED
00 01 02 04 05 06 07
08 09 10 11 12 13 14
15 16 17 18 19
Zones Enabled Screen
ZONES DISABLED
03
Zones Disabled Screen
ZONE SETUP
1=ZONE TYPES
2=ZONES AVAILABLE
3=FUTURE
Zone Setup Screen #3
ZONE TYPE PROG
1=Z00 MONITOR
2=Z01 MONITOR
3=Z02 MONITOR
Zones Installed Screen