Master Programming Level
Programming
ANN-LED Zone Option - Alarm, Trouble and Supervisory
If Zone is selected as the module option, and the module is programmed to annunciate alarms,
troubles, and supervisories, the first ten LEDs on the first ANN-LED module will display the sys-
tem status information. The remaining 30 LEDs on the first module and the last 30 LEDs on the
second module will display the alarm, trouble and supervisory status for each of the ten zones in the
Zone Range programmed for that particular module. The LED assignments for each ANN-LED
module will be as follows.
ANN-RLED Point Option - Alarm Only
If Point is selected as the module option and the module is programmed to annunciate alarms only,
the first ten LEDs on the first ANN-RLED module will display the system status information. The
remaining 30 LEDs on the first module and LEDs 11 - 30 on the second module will display the
active/alarm status of each point in the Point Range programmed for that particular module. The
LED assignments for each ANN-RLED module will be as follows.
Not Used
Not Used
Not Used
Not Used
Not Used
First ANN-LED Module
Alarm Silenced
NAC 1 Fault
NAC 2 Fault
Not Used
Not Used
Earth Fault
Battery Fault
Charger Fault
Disabled
Maintenance
Zone 00
Active/Alarm
Zone 01
Active/Alarm
Zone 02
Active/Alarm
Zone 03
Active/Alarm
Zone 04
Active/Alarm
Zone 00
Trouble
Zone 01
Trouble
Zone 02
Trouble
Zone 03
Trouble
Zone 04
Trouble
Zone 00
Supervisory
Zone 01
Supervisory
Zone 02
Supervisory
Zone 13
Supervisory
Zone 04
Supervisory
Zone 05
Active/Alarm
Zone 06
Active/Alarm
Zone 07
Active/Alarm
Zone 08
Active Alarm
Zone 09
Active/Alarm
Zone 05
Trouble
Zone 06
Trouble
Zone 07
Trouble
Zone 08
Trouble
Zone 09
Trouble
Zone 05
Supervisory
Zone 06
Supervisory
Zone 07
Supervisory
Zone 08
Supervisory
Zone 09
Supervisory
Second ANN-LED Module
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Zone 10
Active/Alarm
Zone 11
Active/Alarm
Zone 12
Active/Alarm
Zone 13
Active/Alarm
Zone 14
Active/Alarm
Zone 10
Trouble
Zone 11
Trouble
Zone 12
Trouble
Zone 13
Trouble
Zone 14
Trouble
Zone 10
Supervisory
Zone 11
Supervisory
Zone 12
Supervisory
Zone 13
Supervisory
Zone 14
Supervisory
Zone 15
Active/Alarm
Zone 16
Active/Alarm‘
Zone 17
Active/Alarm
Zone 18
Active/Alarm
Zone 19
Active/Alarm
Zone 15
Trouble
Zone 16
Trouble
Zone 17
Trouble
Zone 18
Trouble
Zone 19
Trouble
Zone 15
Supervisory
Zone 16
Supervisory
Zone 17
Supervisory
Zone 18
Supervisory
Zone 19
Supervisory
First ANN-RLED Module (Point Range 01 - 30)
Alarm Silenced
NAC 1 Fault
NAC 2 Fault
Not Used
Not Used